Plan Review Notes For Permit 18100307 |
Permit Number |
18100307 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-24 15:31:15 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- CALCULATED DESIGN PRESSURES SUBMITTED ARE INCORRECT. | | ACCORDING TO PLANS ON CITY RECORDS. OPENINGS #1 AND #7 | | ARE LOCATED IN END ZONE NOT INTERIOR ZONE. REVISE AS | | REQUIRED. NOTE: ACCORDING TO NOTE "A" ON FIGURE | | R301.2(7) FBC-RESIDENTIAL END ZONE APPLIES TO OPENINGS | | WITHING 4'-0" IN ALL CASES. REVISE AS REQUIRED. | | | | 2- CLEARLY SPECIFY SIZE OF OPERABLE WINDOWS ON MASTER | | BEDROOM WINDOW TO VERIFY COMPLIANCE WITH THE EGRESS | | REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|