2018-11-06 11:35:16PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 THERE ARE SOME QUESTIONS WITH THE SUBMITTALS THAT NEED
 TO BE ADDRESSED.
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IT IS DIFFICULT TO CORRELATE SOME OF THE EXTERIOR
 CLADDING SUBMITTALS WITH THE PLANS. PROVIDE
 CLARIFICATION AS TO WHERE EACH OF THE PRODUCTS WILL BE
 USED AND THE SPECIFIC APPLICATION OF THE PRODUCT. FBC
 107.2.1
  
 2) THE EXPANDED POLYSTYRENE BOARD LISTING INFORMATION
 IS MISSING PAGE 2. FBC 107.2.1
  
 3) THE ARCHITECT'S SHOP DRAWING REVIEW STAMP OBSCURES
 SOME OF THE INFORMATION ON SOME OF THE SUBMITTAL
 DOCUMENTS. FBC 107.2.1
  
 4) THE HILTI FASTENER CHARTS ON PAGES 73,74 AND 75 OF
 THE CLARK DIETRICH CALCULATIONS ARE ILLEGIBLE. FBC
 107.2.1
  
 5) THE ELEVATIONS APPEAR TO SHOW FAUX STONE AND FAUX
 WOOD PANELS ON THE COLD FORMED STEEL BUILT OUT SECTIONS
 ON THE EXTERIOR WALLS. THE COLD FORMED STEEL FRAMING
 COMPUTATIONS SHOW A TOTAL WALL DEAD LOAD OF 18 PSF FOR
 THE WALLS WHICH INCLUDES THE 5/8" GYP. BOARD, ONE INCH
 OF STUCCO AND THE FRAMING. IT DOES NOT INCLUDE THE DEAD
 WEIGHT OF THE INSTALLED VENEER UNITS WHICH CAN BE AS
 MUCH AS 15 PSF PER SECTION 3.0 DESCRIPTION ON ESR-1215
 OF THE EVALUATION REPORT. FBC 1604.1
  
 6) THE EVALUATION REPORT FOR THE ELDORADO STONE
 ADDRESSES DEFLECTION BUT DOES NOT INDICATE THE
 ALLOWABLE DESIGN WIND PRESSURES FOR THE ATTACHMENT OF
 THE PRODUCT TO THE STUCCO BASE. ACCORDING TO THE
 ELEVATIONS THIS FAUX STONE WILL BE USED IN WALL ZONES
 4, 5, 4P AND 5P. THE COMPONENT AND CLADDING CHARTS ON
 SHEET S-1.11 HAVE NEGATIVE PRESSURES AS HIGH AS -98 PSF
 IN WALL ZONE 5 AND -161 PSF IN ZONES 4P AND 5P AT THE
 PARAPET WALLS. FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD.
  
 7) THE ELDORADO STONE, "VINTAGE RANCH" PRODUCT IS NOT
 ONE OF THE PATTERNS LISTED ON PAGE 3 OF ESR-1215.
 PROVIDE PRODUCT APPROVALS FOR THE VILLAGE RANCH
 CLADDING. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD.
  
 8) PROVIDE PRODUCT APPROVALS OR ENGINEERED CALCULATIONS
 TO SHOW THAT THE STEEL FRAMED BUILT OUT SECTIONS WITH
 THE DENS GLASS, WIRE LATH, STUCCO AND FAUX STONE
 ASSEMBLY WILL WITHSTAND THE WIND LOADS SPECIFIED ON THE
 STRUCTURAL DRAWINGS. FBC 1604.1
  
 9) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.