Notes |
Date |
Text |
2018-10-10 13:18:35 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS | | BUILDING IS LOCATED IN EXPOSURE "D". BASED ON TABLE | | R301.2(4) AND TABLE R301.2(3) FBC-RESIDENTIAL THE | | DESIGN PRESSURES (+38.80PSF/-43.21PSF) ARE HIGHER THAN | | THE DESIGN PRESSURES FOR GARAGE DOOR PRODUCT APPROVAL | | FL16107.7 SUBMITTED (+38PSF/-42PSF). PROVIDE PRODUCT | | APPROVAL FOR DOOR THAT MEETS OR EXCEEDS THE DESIGN | | PRESSURES OR PROVIDE ENGINEERING CALCULATIONS SHOWING | | THAT THE DESIGN PRESSURES ARE LOWER THAN THE REFERENCED | | TABLES. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|