Plan Review Notes
Plan Review Notes For Permit 18100279
Permit Number 18100279
Review Stop B
Sequence Number 5
Notes
Date Text
2019-06-05 10:20:32RESIDENTIAL (R3)ALTERATION/ADDITION FIFTH BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 1- IMPACT FEES: TO BE DONE LATER ONCE PLANS ARE
 APPROVED.
  
 2- ENERGY CALCULATIONS:
  
 A) OK.
  
 ORIGINAL COMMENT:
 B) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. THE NAME OF PERSON DOING
 THE CALCULATIONS WAS NOT PROVIDED AS REQUIRED BY SEC.
 R405.4.2.1. ONLY THE SIGNATURE WAS PROVIDED.
  
 NOTE:
 ARCHITECT'S RESPONSE LETTER STATES THAT "R 405.4.2.1 IS
 COMMERCIAL CODE REFERENCE, BUT FORM IS SIGNED BY MIKEL
 ABBOTT". THIS IS INCORRECT. SECTION CITED IS CORRECT.
 THE FBC CODE-ENERGY CONSERVATION IS DIVIDED INTO
 COMMERCIAL AND RESIDENTIAL. ALL CODE SECTIONS WITH THE
 LETTER "R" BEFORE THE CODE SECTION APPLIES FOR THE
 RESIDENTIAL CODE AND ALL CODE SECTIONS WITH THE LETTER
 "C" BEFORE THE CODE SECTION APPLIES TO THE COMMERCIAL
 PROJECTS. ALSO, THIS SECTION CLEARLY STATES TO PROVIDE
 THE NAME OF THE PERSON DOING THE CALCULATIONS NOT THE
 SIGNATURE.
 I HOPE THIS CLARIFIES THE COMMENT. IF THERE ARE ANY
 QUESTIONS, PLEASE FEEL FREE TO CONTACT ME. I WILL BE
 MORE THAN HAPPY TO ANSWER ANY QUESTION TO AVOID MORE
 DELAYS. AS YOU CAN SEE ON TOP OF THIS CHECKLIST, I WANT
 TO PASS THIS BUILDING REVIEW WITH A PROVISO BUT FEES
 WOULD APPLY IF THE CORRECTIONS ARE DONE AFTER THE
 PERMIT IS ISSUED. THANK YOU.
  
 ORIGINAL COMMENT:
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME AND JURISDICTION NUMBER (THIS
 JURISDICTION IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 PARTIALLY ADDRESSED. PROVIDE COMPLETE NAME OF THE
 BUILDER. NAME PROVIDED DOESN'T MATCH NAME OF
 CONTRACTOR.
  
 D) OK.
  
 ORIGINAL COMMENT:
 E)ROOF TYPE AND MATERIAL SPECIFIED ON PAGE 2 OF 4
 DOESN'T MATCH. SEE PLANS AND PRODUCT APPROVALS. REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 PARTIALLY ADDRESSED. THE ROOF MATERIAL WAS REVISED BUT
 THE TYPE OF ROOF WAS NOT. SEE PLANS AND REVISE AS
 REQUIRED TO MATCH.
  
 F) OK.
  
 ORIGINAL COMMENT:
 G)WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS. WINDOW AREA DOESN'T MATCH. NOTE: DOORS WITH
 GLAZING NEED TO BE ENTERED IN THE WINDOW AREA ALSO.
 OVERHANG DEPTH AND SEPARATION DOESN'T MATCH PLANS.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 CALCULATIONS ARE DONE FOR THE ADDITION ONLY. THERE ARE
 NOT WINDOWS ON THE NORTH SIDE OF THE ADDITION. GLASS
 AREA IN THE MASTER BEDROOM NEED TO BE COUNTED. THE
 WINDOWS OVERHANG SEPARATING DOESN'T MATCH PLANS. REVISE
 AS REQUIRED.
  
 3- OK.
  
 4- OK.
  
 5- OK.
  
 6- OK.
  
 7- OK.
  
 8- OK.
  
 9- OK.
  
 10- OK.
  
 11- OK.
  
 12- OK.
  
 13- OK.
  
 14- OK.
  
 15- OK.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  