2019-06-05 10:20:32 | RESIDENTIAL (R3)ALTERATION/ADDITION FIFTH BUILDING |
| REVIEW CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO |
| ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR |
| IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| |
| |
| 1- IMPACT FEES: TO BE DONE LATER ONCE PLANS ARE |
| APPROVED. |
| |
| 2- ENERGY CALCULATIONS: |
| |
| A) OK. |
| |
| ORIGINAL COMMENT: |
| B) PROVIDE THE NAME OF THE PERSON DOING THE |
| CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY |
| CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. THREE TIMES. THE NAME OF PERSON DOING |
| THE CALCULATIONS WAS NOT PROVIDED AS REQUIRED BY SEC. |
| R405.4.2.1. ONLY THE SIGNATURE WAS PROVIDED. |
| |
| NOTE: |
| ARCHITECT'S RESPONSE LETTER STATES THAT "R 405.4.2.1 IS |
| COMMERCIAL CODE REFERENCE, BUT FORM IS SIGNED BY MIKEL |
| ABBOTT". THIS IS INCORRECT. SECTION CITED IS CORRECT. |
| THE FBC CODE-ENERGY CONSERVATION IS DIVIDED INTO |
| COMMERCIAL AND RESIDENTIAL. ALL CODE SECTIONS WITH THE |
| LETTER "R" BEFORE THE CODE SECTION APPLIES FOR THE |
| RESIDENTIAL CODE AND ALL CODE SECTIONS WITH THE LETTER |
| "C" BEFORE THE CODE SECTION APPLIES TO THE COMMERCIAL |
| PROJECTS. ALSO, THIS SECTION CLEARLY STATES TO PROVIDE |
| THE NAME OF THE PERSON DOING THE CALCULATIONS NOT THE |
| SIGNATURE. |
| I HOPE THIS CLARIFIES THE COMMENT. IF THERE ARE ANY |
| QUESTIONS, PLEASE FEEL FREE TO CONTACT ME. I WILL BE |
| MORE THAN HAPPY TO ANSWER ANY QUESTION TO AVOID MORE |
| DELAYS. AS YOU CAN SEE ON TOP OF THIS CHECKLIST, I WANT |
| TO PASS THIS BUILDING REVIEW WITH A PROVISO BUT FEES |
| WOULD APPLY IF THE CORRECTIONS ARE DONE AFTER THE |
| PERMIT IS ISSUED. THANK YOU. |
| |
| ORIGINAL COMMENT: |
| C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING BUILDER NAME AND JURISDICTION NUMBER (THIS |
| JURISDICTION IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| RESPONSE: |
| PARTIALLY ADDRESSED. PROVIDE COMPLETE NAME OF THE |
| BUILDER. NAME PROVIDED DOESN'T MATCH NAME OF |
| CONTRACTOR. |
| |
| D) OK. |
| |
| ORIGINAL COMMENT: |
| E)ROOF TYPE AND MATERIAL SPECIFIED ON PAGE 2 OF 4 |
| DOESN'T MATCH. SEE PLANS AND PRODUCT APPROVALS. REVISE |
| AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| PARTIALLY ADDRESSED. THE ROOF MATERIAL WAS REVISED BUT |
| THE TYPE OF ROOF WAS NOT. SEE PLANS AND REVISE AS |
| REQUIRED TO MATCH. |
| |
| F) OK. |
| |
| ORIGINAL COMMENT: |
| G)WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH |
| PLANS. WINDOW AREA DOESN'T MATCH. NOTE: DOORS WITH |
| GLAZING NEED TO BE ENTERED IN THE WINDOW AREA ALSO. |
| OVERHANG DEPTH AND SEPARATION DOESN'T MATCH PLANS. |
| REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| CALCULATIONS ARE DONE FOR THE ADDITION ONLY. THERE ARE |
| NOT WINDOWS ON THE NORTH SIDE OF THE ADDITION. GLASS |
| AREA IN THE MASTER BEDROOM NEED TO BE COUNTED. THE |
| WINDOWS OVERHANG SEPARATING DOESN'T MATCH PLANS. REVISE |
| AS REQUIRED. |
| |
| 3- OK. |
| |
| 4- OK. |
| |
| 5- OK. |
| |
| 6- OK. |
| |
| 7- OK. |
| |
| 8- OK. |
| |
| 9- OK. |
| |
| 10- OK. |
| |
| 11- OK. |
| |
| 12- OK. |
| |
| 13- OK. |
| |
| 14- OK. |
| |
| 15- OK. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |
| |