2019-01-23 11:46:55 | RESIDENTIAL (R3)ALTERATION/ADDITION SECOND BUILDING |
| REVIEW CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- IMPACT FEES: TO BE DONE LATER ONCE PLANS ARE |
| APPROVED. |
| |
| 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| BY SEC. 1106 FBC-EXISTING BUILDING. |
| NOTE: COORDINATE WITH PLANS AND PRODUCT APPROVALS TO |
| AVOID CONFLICTS/DELAYS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| |
| 3- DRAINAGE |
| PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: |
| FBC R 401.3 (DRAINAGE) |
| FBC 107.2.5 (SITE PLAN) |
| FBC 110.9 (IMPACT OF CONSTRUCTION) |
| |
| RESPONSE: |
| DRAINAGE PLAN SUBMITTED DOESN'T SEEM TO COMPLY WITH |
| SEC. R401.3 FBC-RESIDENTIAL. ALSO, IT LOOKS LIKE IS |
| CREATING A HAZARD BY HAVING AN 8" DROP IN THE WALKING |
| SURFACE. THE SWALES SHOWN ARE MORE LIKE RETENTION PONDS |
| RATHER THAN SWALES THAT DIVERT THE WATER AWAY FROM THE |
| BUILDING. THE RETENTION POND BETWEEN THE ADDITION AND |
| ADJACENT NEIGHBOR LOOKS LIKE IT MAY BE CREATING A POND |
| PROBLEM TO THE NEIGHBOR AND TO THE ADDITION ITSELF. |
| ALSO, DRAINAGE CALCULATIONS SUBMITTED DON'T SEEM TO BE |
| ADEQUATE. WHERE ARE THE COEFFICIENTS TAKEN FROM?. SEE |
| FIGURE 1106.1 FBC-PLUMBING FOR RAINFALL RATES IN |
| FLORIDA. ALSO, SIZES OF GUTTERS AND RAIN LEADERS SHOWN |
| IN THE DRAINAGE PLAN ARE ARE NOT SPECIFIED. REVISE |
| DRAINAGE PLAN AS REQUIRED. |
| |
| 4- SHEET A-2.2: |
| A) OK. |
| |
| B)OK. |
| |
| C) OK. |
| |
| D) PROVIDE COMPLETE SPECIFICATIONS FOR THE DOOR LEADING |
| FROM THE GARAGE TO THE MAIN HOUSE SHOWING COMPLIANCE |
| WITH SEC. R302.5.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| IT LOOKS LIKE THERE ARE WINDOWS ADJACENT TO THE DOOR |
| LEADING FROM THE PROPOSED GARAGE TO THE INTERIOR OF THE |
| HOUSE. ALL OPENINGS LEADING TO THE HOUSE NEED TO COMPLY |
| WITH SEC. R302.5.1 FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| |
| E) OK |
| |
| F) OK. |
| |
| G) OK. |
| |
| H) SPECIFY ATTIC ACCESS SIZE AND LOCATION IN THE |
| ADDITION SEC. R307.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| LOCATION OF PROPOSED ATTIC ACCESS DOESN'T SEEM TO |
| PROVIDE THE REQUIRED HEIGHT CLEARANCE ABOVE THE |
| OPENING. REVISE AS REQUIRED. |
| |
| 5- OK. |
| |
| 6- OK. |
| |
| 7- SHEET A-2.0: |
| A) OK. |
| |
| B) FLOOD INFORMATION SHOWN UNDER EXISTING SITE DATA |
| DOESN'T SEEM TO BE CORRECT. CLARIFY WHY SUBMITTING THIS |
| INFORMATION IF THE PROPERTY IS NOT LOCATED IN A SPECIAL |
| FLOOD ZONE AREA. ALSO, CLARIFY/REVISE NOTES AT THE |
| BOTTOM OF AREA CALCULATIONS. FLOOD ELEVATION |
| CERTIFICATE IS NOT REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| RESPONSE: |
| FLOOD INFORMATION SEEMS TO BE INCORRECT. PROPERTY IS NO |
| LOCATED IN A SPECIAL FLOOD HAZARD AREA. CLARIFY WHERE |
| IS THIS INFORMATION TAKEN FROM. OTHERWISE, REMOVE |
| INFORMATION TO AVOID CONFUSION. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| C)OK. |
| |
| 8- OK. |
| |
| 9- OK. |
| |
| 10- OK. |
| |
| 11- OK. |
| |
| 12- OK. |
| |
| 13- OK. |
| |
| 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A)OVERHEAD GARAGE DOOR AS SHOWN ON PLANS. |
| |
| RESPONSE: |
| PROVIDE 2 COPIES OF NOA 16-0906.06. ONLY ONE WAS |
| SUBMITTED. |
| |
| B) EXTERIOR SWING GARAGE DOOR AS SHOWN ON PLANS. |
| |
| RESPONSE: |
| PROVIDE 2 COPIES OF NOA 15-0611.05. ONLY ONE WAS |
| SUBMITTED. |
| |
| C) ROOF FINISH (SHINGLES?) |
| |
| RESPONSE: |
| PROVIDE 2 COPIES OF NOA 14-1022.09. ONLY ONE WAS |
| SUBMITTED. |
| |
| D)OK. |
| |
| 15- OK. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |
| |