2018-10-30 08:00:19 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ELECTRICAL NOTES SAY THE ADDIDTION WILL BE DONE TO |
| THE 2011 NATIONAL ELECTRIC CODE. 2014 IS THE CURRENT |
| NATIONAL ELECTRICAL CODE AND IS THE APPLICABLE CODE FOR |
| THIS PROJECT. PROVIDE CORRECTION. FBC 107.2.1 |
| |
| 2. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON |
| RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS |
| 481.229; WPB FBC 107.2.1, 107.3.5.1.2 |
| |
| 3. LOAD CALCULATION IS NOT ACCURATE. PROVIDE ACCURATE |
| LOAD CALCULATION INCLUDING ALL LOADS. NEC 220; FBC RE |
| E3602.2 |
| |
| 4. MISSING RECEPTACLE RIGHT OF EXTERIOR DOOR IN NEW |
| MASTER BEDROOM. 210.52A1 NEC |
| |
| 5. MISSING RECEPTACLE RIGHT OF CLOSET DOOR IN NEW |
| MASTER BEDROOM. 210.52A1 NEC |
| |
| 6. SMOKE/CARBON COMBO ALARM REQUIRED OUTSIDE BEDROOMS |
| (NEW AND EXISITING) DUE TO NEW PROPOSED ATTACHED |
| GARAGE. FBC R314 & 315 |
| |
| 7. RECEPTACLE REQUIRED IN GARAGE. 210.52G1 |
| |
| 8. ALL RECEPTACLES IN GARAGE MUST BE GFCI PROTECTED. |
| 210.8A2 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-657-1653 |
| |