2018-11-21 10:42:38RESIDENTIAL (R3)ALTERATION/ADDITION BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- IMPACT FEES - PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 1106 FBC-EXISTING BUILDING.
 NOTE: COORDINATE WITH PLANS AND PRODUCT APPROVALS TO
 AVOID CONFLICTS/DELAYS.
  
 3- DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 SEC. R401.3 FBC_RESIDENTIAL:
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. IN THE CASE OF
 DEMOLITION, THE SITE PLAN SHALL SHOW CONSTRUCTION TO BE
 DEMOLISHED AND THE LOCATION AND SIZE OF EXISTING
 STRUCTURES AND CONSTRUCTION THAT ARE TO REMAIN ON THE
 SITE OR PLOT. THE BUILDING OFFICIAL IS AUTHORIZED TO
 WAIVE OR MODIFY THE REQUIREMENT FOR A SITE PLAN WHEN
 THE
 APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR OR
 WHEN OTHERWISE WARRANTED.
  
 SEC. 110.9 CITY AMENDMENTS: IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS
 OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE
 CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS
 OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY
 PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE
 DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION,
 PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A CERTIFICATION FROM A
 LICENSED PROFESSIONAL SHALL BE SUBMITTED TO THE
 INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE FINAL
 INSPECTION.
  
  
 4- SHEET A-2.2:
 A) PROPOSED FLOOR PLAN DOESN'T HAVE ANY ROOM
 DIMENSIONS. NEED TO PROVIDE DIMENSIONS OF ALL AREAS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B)PROPOSED FLOOR PLAN SHOWS ONE WINDOW OF EXISTING
 BEDROOM TO BE BLOCKED TO ALLOW FOR THE ADDITION.
 SPECIFY SIZE AND TYPE OF EXISTING WINDOWS IN THIS
 BEDROOM TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 701.2 AND SEC. 702.5 FBC-EXISTING
 BUILDING OF WINDOW TO REMAIN.
  
 C) DOOR SCHEDULE NEEDS TO INCLUDE THE NEW GARAGE
 OVERHEAD DOOR AND EXTERIOR SWING DOOR. SEC. 107.2.1
 CITY AMENDMENTS.
  
 D) PROVIDE COMPLETE SPECIFICATIONS FOR THE DOOR LEADING
 FROM THE GARAGE TO THE MAIN HOUSE SHOWING COMPLIANCE
 WITH SEC. R302.5.1 FBC-RESIDENTIAL.
  
 E) PROVIDE STRUCTURAL BUCK DETAIL AND SPECIFICATIONS
 FOR NEW OVERHEAD GARAGE DOOR. SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: PROVIDE STRUCTURAL BUCK DETAIL FOR ALL EXTERIOR
 SWING DOORS ALSO.
  
 F) FLOOR PLAN SHOWS AN EXISTING "FAMILY ROOM".
 ACCORDING TO CITY RECORDS AND PROPERTY APPRAISER THIS
 ROOM IS AN "ENCLOSED PORCH" NOT LIVABLE AREA. THERE ARE
 NO PERMITS SHOWING CONVERSION OF THIS ROOM. REVISE NAME
 OF ROOM TO ENCLOSED PORCH OR PROVIDE COMPLETE DRAWINGS
 AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE ROOM
 CONVERSION TO LIVABLE SPACE. SEC. 105.1 CITY
 AMENDMENTS.
  
 G) CLARIFY DOORS "B" AND "C" SPECIFIED IN THE DOOR
 SCHEDULE. ARE THESE REALLY ALUM/GLASS FRENCH DOORS?.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 H) SPECIFY ATTIC ACCESS SIZE AND LOCATION IN THE
 ADDITION SEC. R307.1 FBC-RESIDENTIAL.
  
 5- SPECIFY CARBON MONOXIDE ALARM WITHING ALL SLEEPING
 ROOMS, INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC.
 R315.1 FBC-RESIDENTIAL.
  
 6- LIST OF DRAWINGS SHOWN ON SHEET TS-1 DON'T MATCH
 DRAWINGS SUBMITTED. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 7- SHEET A-2.0:
 A) HATCHED AREA SQUARE FOOTAGE SPECIFIED ON THE SITE
 PLAN BY THE "NEW ADDITION" DOESN'T MATCH TOTAL
 ADDITIONAL A/C SPACE SHOWN IN THE AREA CALCULATIONS IN
 THE SAME SHEET. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) FLOOD INFORMATION SHOWN UNDER EXISTING SITE DATA
 DOESN'T SEEM TO BE CORRECT. CLARIFY WHY SUBMITTING THIS
 INFORMATION IF THE PROPERTY IS NOT LOCATED IN A SPECIAL
 FLOOD ZONE AREA. ALSO, CLARIFY/REVISE NOTES AT THE
 BOTTOM OF AREA CALCULATIONS. FLOOD ELEVATION
 CERTIFICATE IS NOT REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 C)REVISE/CLARIFY THE "RESTORATION LEVEL" SPECIFIED
 UNDER "EXISTING BUILDING RENOVATION". THIS IS NOT
 RESTORATION LEVEL 3. THIS IS ALTERATION LEVEL 2 AND
 ADDITION. SEC. 504 AND 507 FBC-EXISTING BUILDING.
  
 8- SHEET A-5.0: SPECIFY COLUMNS AND BEAM/LINTEL AT THE
 ENDS OF OVERHEAD GARAGE DOOR AND EXTERIOR SWING DOORS
 IN NEW GARAGE
 SEC. R301.1 FBC-RESIDENTIAL.
  
 9- SPECIFY ROOF CROSS VENTILATION AS REQUIRED BY SEC.
 R806 FBC-RESIDENTIAL. SPECIFY SIZE AND LOCATION.
  
 10- PROVIDE ROOF SHEATHING NAIL TYPE, SIZE AND SPACING
 AS REQUIRED BY SEC. R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: NEED TO SPECIFY RING SHANK NAILS AND GABLE ROOFS
 ENDS ARE IN ZONE #3 (5'-0" MIN.).
  
 11- FLOOR INFORMATION SHOWN ON WALL SECTION "B" ON
 SHEET A-5.5 DOESN'T MATCH FOUNDATION PLANS ON SHEET
 A-5.0. SEC. 107.2.1 CITY AMENDMENTS.
  
 12- CLARIFY ROOFING INFORMATION SHOWN ON WALL SECTION
 "A" ON SHEET A-5.5. IS IT CONCRETE TILE OR ASPHALT
 SHINGLES?. MAIN HOUSE HAS SHINGLES. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 13- THERE ARE MANY SHEETS THAT REFERENCE THE 2014 CODE.
 UPDATE AS REQUIRED. THE CURRENT CODE IS THE FBC 6TH
 EDITION (2017) NOT THE FBC 5TH EDITION (2014). CHAPTER
 553 FLORIDA STATUTE. UPDATE ALL PLANS AS REQUIRED.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A)OVERHEAD GARAGE DOOR AS SHOWN ON PLANS.
  
 B) EXTERIOR SWING GARAGE DOOR AS SHOWN ON PLANS.
  
 C) ROOF FINISH (SHINGLES?)
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712