Plan Review Notes
Plan Review Notes For Permit 18100232
Permit Number 18100232
Review Stop G
Sequence Number 1
Notes
Date Text
2018-10-23 10:41:031) PLACE A NOTE ON THE PLANS THAT THE GENERATOR EXHAUST
 SHALL BE LOCATED A MINIMUM OF 10 FT. FROM BUILDING
 OPENINGS OR AS PER MANUF. INSTALLATION MANUAL.
 2) THE ORIGINAL GAS PLAN ON FILE IN THE CITY RECORDS
 SHOWS THE LONGEST RUN AT 100 FEET. THIS DISTANCE SHALL
 BE USED IN THE SIZING OF ALL THE GAS PIPING. 2017
 FBC-FUEL GAS SEC. 402.4.1, NOT 15 FEET.
 3) THE MINIMUM SIZE METALLIC PIPE AT THE OUTLET OF THE
 GAS METER SHALL BE 1 1/2 INCHES FOR A LESS THAN 2 PSI
 SYSTEM ACCORDING TO TABLE 402.4 (2) OF THE 2017
 FBC-FUEL GAS CODE.
 4) THE MINIMUM SIZE OF THE PE PIPE SHALL BE 1 1/4 INCH
 PER TABLE 402.4 (21) OF THE 2017 FBC-FUEL GAS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  