Plan Review Notes For Permit 18100200 |
Permit Number |
18100200 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-09 17:38:55 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. SEE FBC B 603.1, ALLOWABLE MATERIALS IN NON | | COMBUSTIBLE BUILDINGS, SEE ITEM 2, EXCEPTION 2, | | ACOUSTICAL INSULATION INSTALLED BETWEEN A FINISHED | | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE | | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT | | MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN | | ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | A FLAME SPREAD TEST WAS PROVIDED BUT THE SPECIMEN WAS | | TESTED WITH THE NONCOMBUSTIBLE BOARD TOWARDS THE FLAME. | | IT IS NOT CLEAR WHY THE UNDERLAYMENT (OR LVT FLOORING) | | WAS NOT FACING THE FLAME. COMPLIANCE NOT CLEAR. EITHER | | PROVIDE RATIONALE FOR TESTING IN THIS MANNER OR PROVIDE | | A TEST WITH THE UNDERLAYMENT TOWARDS THE FLAME. | | | | |
|