2018-10-10 15:57:22RESIDENTIAL (R3) REVISION MECHANICAL REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 1- THERE IS AN ENGINEER OF RECORD ON APPROVED
 MECHANICAL PLAN M-1. ENGINEER OF RECORD NEEDS TO SIGN
 AND SEAL REVISED MECHANICAL PLAN. NEED TO HAVE THE
 ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF RECORD
 AS REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER 471
 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 2- THE REVISED TRANSFER DUCT IN THE MASTER BEDROOM
 DOESN'T COMPLY WITH THE BALANCED RETURN AIR SEC.
 M1602.4 FBC-RESIDENTIAL. NEED AT LEAST 13" DUCT.
 ORIGINAL APPROVED PLAN CALLED FOR 14" TRANSFER DUCT AND
 14"X14" RAG. REVISE AS REQUIRED.
  