2018-10-10 15:57:22 | RESIDENTIAL (R3) REVISION MECHANICAL REVIEW COMMENTS | | CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS. | | | | 1- THERE IS AN ENGINEER OF RECORD ON APPROVED | | MECHANICAL PLAN M-1. ENGINEER OF RECORD NEEDS TO SIGN | | AND SEAL REVISED MECHANICAL PLAN. NEED TO HAVE THE | | ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF RECORD | | AS REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER 471 | | F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC | | RECORDS. | | | | 2- THE REVISED TRANSFER DUCT IN THE MASTER BEDROOM | | DOESN'T COMPLY WITH THE BALANCED RETURN AIR SEC. | | M1602.4 FBC-RESIDENTIAL. NEED AT LEAST 13" DUCT. | | ORIGINAL APPROVED PLAN CALLED FOR 14" TRANSFER DUCT AND | | 14"X14" RAG. REVISE AS REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|