2018-10-15 18:54:45RESIDENTIAL (R2) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- RAS 117 CALCULATIONS:
 A) ENGINEER TO REVISE RAS 117 CALCULATIONS. ACCORDING
 TO SEC. 1609.4 FBC THIS BUILDING-IS LOCATED IN EXPOSURE
 "D" NOT "C". EACH WIND DIRECTION NEED TO BE CONSIDERED
 TO DETERMINE THE BUILDING EXPOSURE. THE SOUTH WEST
 QUADRANT OF THIS BUILDING REFLECTS AN EXPOSURE D. SEE
 AERIAL VIE OF THE BUILDING AND REVISE CALCULATIONS AS
 REQUIRED.
  
 B) THIS IS A TWO STORY APARTMENT BUILDING WITH 12
 APARTMENTS NOT A SINGLE FAMILY RESIDENCE AS SPECIFIED
 ON THE CALCULATIONS. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 2- PERMIT APPLICATION SPECIFIES THAT THIS IS A ONE
 STORY 10 FT BUILDING. THIS IS INCORRECT. THIS IS A TWO
 STORY APARTMENT BUILDING. PROVIDE CORRECT INFORMATION
 THAT MATCHES BUILDING INFORMATION. SEC. 107.2.1 CITY
 AMENDMENTS AND CITY POLICY FOR ROOFING PERMITS.
  
  