2018-10-15 18:54:45 | RESIDENTIAL (R2) RE-ROOF BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- RAS 117 CALCULATIONS: | | A) ENGINEER TO REVISE RAS 117 CALCULATIONS. ACCORDING | | TO SEC. 1609.4 FBC THIS BUILDING-IS LOCATED IN EXPOSURE | | "D" NOT "C". EACH WIND DIRECTION NEED TO BE CONSIDERED | | TO DETERMINE THE BUILDING EXPOSURE. THE SOUTH WEST | | QUADRANT OF THIS BUILDING REFLECTS AN EXPOSURE D. SEE | | AERIAL VIE OF THE BUILDING AND REVISE CALCULATIONS AS | | REQUIRED. | | | | B) THIS IS A TWO STORY APARTMENT BUILDING WITH 12 | | APARTMENTS NOT A SINGLE FAMILY RESIDENCE AS SPECIFIED | | ON THE CALCULATIONS. REVISE AS REQUIRED. SEC. 107.2.1 | | CITY AMENDMENTS. | | | | 2- PERMIT APPLICATION SPECIFIES THAT THIS IS A ONE | | STORY 10 FT BUILDING. THIS IS INCORRECT. THIS IS A TWO | | STORY APARTMENT BUILDING. PROVIDE CORRECT INFORMATION | | THAT MATCHES BUILDING INFORMATION. SEC. 107.2.1 CITY | | AMENDMENTS AND CITY POLICY FOR ROOFING PERMITS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|