Plan Review Notes For Permit 18100150 |
Permit Number |
18100150 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-04 16:26:11 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- FLAT ROOF: ENGINEER TO REVISE RAS 117 CALCULATIONS | | SUBMITTED. ENGINEER IS ROUNDING UP THE FASTENER | | SPACING. ACCORDING TO SEC. 104.5 OF RAS 117 THE | | FASTENER SPACING SHALL BE ROUNDED DOWN TO THE NEXT | | WHOLE NUMBER NOT ROUNDED UP. REVISE FASTENER SPACING AS | | REQUIRED. NOTE: KEEP IN MIND THAT THE MINIMUM FASTENER | | SEPARATION SHALL NOT BE LESS THAN 4 INCHES O.C.. SEE | | SEC. 8.1 OF RAS 117. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|