2019-01-30 14:32:362ND REVIEW FBC-2010 MECHANICAL
 REVISION #18100146
 MASTER #15111020
 1/30/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE- 2010
 FBC M- FLORIDA MECHANICAL CODE- 2010
 FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE LETTER FROM DAVE LUCAS- REGIONAL DIRECTOR OF
 CARRIER ENTERPRISE CERIFYING THE INSTALLATION OF THE
 AC/P1-1 AND P1-2 OUTDOOR CONDENSERS IN THE PARKING
 GARAGE IS NOT ACCEPTED BECAUSE THE LETTER IS NOT
 ADDRESSING THE ACTUAL INSTALLATION LOCATIONS IN THE
 ENCLOSED PARKING GARAGE. MR.LUCAS'S LETTER IS
 ADDRESSING CONDENSERS IN "OUTDOOR ENVIRONMENTS AND
 WITHIN OPEN VENTILATED COVERED AREAS WHERE AIR FLOW
 CLEARANCES MEET WITH THE MINIMAL REQUIREMENTS AS SET
 FORTH IN THE PRODUCT INSTALLATION INSTRUCTIONS." THE
 INTERIOR OF THE WALL OF THE ENCLOSED PARKING GARAGE IS
 NOT CONSIDERED AN OUTDOOR, OR OPEN VENTILATED COVERED
 AREA, PROVIDE A REVISED LETTER THAN PROVIDES MORE
 INFORMATION AND EVIDENCE OF COMPLIANCE, OR RELOCATE THE
 CONDENSERS TO THE OUTDOORS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER