Plan Review Notes
Plan Review Notes For Permit 18100146
Permit Number 18100146
Review Stop E
Sequence Number 1
Notes
Date Text
2018-10-22 17:46:34FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E1.01L
  
 PLEASE PROVIDE CUT SHEETS FOR WATER FEATURE LIGHTS
  
 PAGE E2.27
  
 SYMBOL FOR OUTLETS SHOWN ON ROOF NOT IN LEGEND
  
 CIRCUIT LRN 33, 35 NOT SHOWN ON PANEL SCHEDULE.ON PAGE
 E6.13
  
 CIRCUITS LRN 33, 35 TO BE GFCI PROTECTED
  
 PAGE E5.01
  
 PH 24 RISER MSN-4 SIZE OF MAIN TO A1N NOT SHOWN
 ATS-N, AND ATS-S SIZES NOT SHOWN
 B1N, AND B1S SIZE NOT SHOWN
 LRN4 AND LRS4 SIZE NOT SHOWN
  
  