Plan Review Notes
Plan Review Notes For Permit 18100126
Permit Number 18100126
Review Stop B
Sequence Number 1
Notes
Date Text
2018-10-18 14:34:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SCOPE NOT CLEAR. THE PERMIT APPLICATION STATES:
 "REMOVE AND REPLACE CONCRETE ROOF TILES DUE TO
 HURRICANE IRMA DAMAGE."
  
 SEE FBC EB 706.1.1. ONLY 25% OF THE ROOF CAN BE
 REPAIRED; OTHERWISE A REROOF IS REQUIRED. IT APPEARS
 THAT A REROOF IS PROPOSED AS UNDERLAYMENT NOA WAS
 PROVIDED.
  
 EITHER PROVIDE A NEW PERMIT APPLICATION WHICH INDICATES
 THAT SCOPE OF WORK IS "REROOF, REPLACE EXISTING TILE
 ROOF WITH NEW" OR PROVIDE A PLAN WHICH CLEARLY SHOWS
 SCOPE OF WORK - SQUARE FOOT AREA, AREA TO BE REPLACED,
 SCOPE OF REPLACEMENT (TILES ONLY AS APPLICATION
 INDICATES OR REPLACEMENT OF UNDERLAYMENT AND TILES),
 TOTAL SQUARE FOOT AREA OF ROOF.
  
 2. ON THE TILE PRODUCT APPROVAL, INDICATE WHICH METHOD
 OF ATTACHMENT IS PROPOSED (PADDY SIZE).
  