2018-10-23 16:14:06 | SHUTTERS SECOND BUILDING REVIEW CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| FLORIDA PRODUCT APPROVAL FL17080-R2 IS NOT DESIGNED FOR |
| STEEL FRAMED APPLICATION. NEED PRODUCT APPROVAL THAT IS |
| DESIGNED FOR PROPOSED INSTALLATION. OR SITE SPECIFIC |
| PROJECTS USING THIS PRODUCT APPROVAL SHALL BE SUBMITTED |
| TO THE PRODUCT APPROVAL ENGINEER FOR REVIEW AS REQUIRED |
| BY NOTE 12(D) ON SHEET 1 OF 13. IF USING THIS PRODUCT |
| APPROVAL, THEN NEED THE APPROVAL OF THE PRODUCT |
| APPROVAL ENGINEER OF RECORD. SEC. 107.2.1 CITY |
| AMENDMENTS AND FAC 61G20-3.001. |
| |
| RESPONSE: |
| A) TALKED TO BUILDING OFFICIAL. EVEN THOUGHT IT LOOKS |
| LIKE THE NOTE IMPLIES TO SENT DRAWINGS TO THE P.E.D. |
| ENGINEER. NO NEED TO SEND DRAWINGS TO PRODUCT APPROVAL |
| ENGINEER OF RECORD. ENGINEER OF RECORD WILL BE THE |
| ENGINEER PROVIDING THE SITE SPECIFIC INSTALLATION USING |
| THIS PRODUCT APPROVAL. |
| |
| B) SITE SPECIFIC DRAWINGS NEED TO PROVIDE ALL THE SITE |
| SPECIFIC INFORMATION, INCLUDING ALL THE INFORMATION |
| SHOWN IN THE INSTALLATION SCHEDULE. NEED TO SPECIFY THE |
| SPECIFIC SHUTTER MOUNTING CONDITION ("C4" IS NOT A |
| MOUNTING CONDITION); SHUTTER GLASS SEPARATION; SHUTTER |
| SPAN, EDGE DISTANCE, ANCHOR TYPE AND SPACING (TOP & |
| BOTTOM). SEC. 107.2.1 CITY AMENDMENTS. |
| |
| NOTE: INFORMATION SHOWN ON THE INSTALLATION SCHEDULE |
| AND THE SITE SPECIFIC DRAWINGS DON'T MATCH. CHECK |
| OPENINGS SIZES, ANCHOR TYPE, ETC. |
| |
| |