2018-10-23 10:03:28SHUTTERS SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- THE SUBSTRATE FOR THE PROPOSED INSTALLATION IS STEEL
 FRAME. ACCORDING TO NOTE #8 ON SHEET 1 OF 13 OF
 ACCORDION SHUTTERS FLORIDA PRODUCT APPROVAL FL17080-R2
 SUBMITTED "THIS SHUTTER SHALL ONLY BE ATTACHED TO
 CONCRETE, BLOCK OR WOOD FRAME BUILDINGS." THEREFORE,
 THIS PRODUCT APPROVAL CAN NOT BE USED. PROVIDE PRODUCT
 APPROVAL THAT COVERS EXISTING SUBSTRATE ATTACHMENT.
 NOTE: REVISE SHUTTERS INSTALLATION SCHEDULE
 ACCORDINGLY.
 SEC. 107.2.1 CITY AMENDMENTS AND FAC 61G20-3.001
  
 RESPONSE:
 FLORIDA PRODUCT APPROVAL FL17080-R2 IS NOT DESIGNED FOR
 STEEL FRAMED APPLICATION. NEED PRODUCT APPROVAL THAT IS
 DESIGNED FOR PROPOSED INSTALLATION. OR SITE SPECIFIC
 PROJECTS USING THIS PRODUCT APPROVAL SHALL BE SUBMITTED
 TO THE PRODUCT APPROVAL ENGINEER FOR REVIEW AS REQUIRED
 BY NOTE 12(D) ON SHEET 1 OF 13. IF USING THIS PRODUCT
 APPROVAL, THEN NEED THE APPROVAL OF THE PRODUCT
 APPROVAL ENGINEER OF RECORD.
  