2018-10-16 14:59:37 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL |
| BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| AFCI AND GFCI PROTECTION. PROVIDE CORRECTION TO AFCI |
| NOTE. NEC 210.8, 210.12; FBC RE E3902 |
| 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10; FBC RE E3606.3 |
| 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| NEC 110.3, 110.9; FBC RE E3603.3 |
| 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| CURRENT NOTE NEEDS TO BE CORRECTED. FBC EC C405.1, |
| R404.1 |
| 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 6. KEYNOTE 8 STATES THAT A PULL CHAIN FIXTURE SHALL BE |
| INSTALLED IN CLOSET. IT APPEARS THAT THE CLEARANCE |
| BETWEEN THE LIGHT FIXTURE AND THE CLOSET STORAGE SPACE |
| IS NOT CODE COMPLIANT. PROVIDE CLARIFICATION AND/OR |
| CORRECTION. NEC 410.16; FBC RE E4003.12 |
| 7. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. |
| PROVIDE CORRECTION FOR MASTER BATH. NEC 210.11(C)(3), |
| 210.52(D); FBC RE E3703.4, E3901.6 |
| 8. PANEL SCHEDULE SHOWS THE BATHROOM RECEPTACLE CIRCUIT |
| ON 14 GAUGE WIRE AND A 15 AMP BREAKER. PROVIDE |
| CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE |
| E3703.4, E3901.6 |
| 9. PLAN SHOWS BATHROOM LIGHTING AND RECEPTACLES ON THE |
| SAME CIRCUIT FEEDING 2 BATHROOM, WHICH IS A CODE |
| VIOLATION. PROVIDE CORRECTION. NEC 210.11(C)(3), |
| 210.52(D); FBC RE E3703.4, E3901.6 |
| 10. ELECTRICAL NOTE 8 STATES ONLY 20 AMP RECEPTACLES |
| ARE TO BE TAMPER RESISTANT, AND THIS CONFLICTS WITH |
| OTHER NOTE THAT STATES ALL PER CODE SHALL BE TR. |
| CORRECT DISCREPANCY. NEC 406.12; FBC RE E4002.14 |
| 11. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM |
| BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET |
| FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE |
| R314.3(4), NFPA 72:29.8.3.4 |
| 12. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |