2018-11-07 14:12:13 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18100063 |
| REVIEWED: NOVEMBER 7, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC A = FBC ACCESSIBILITY |
| FBC ENERGY = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. [FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL PLAN TO KEEP |
| CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES |
| AND STORM DRAINS DURING CONSTRUCTION. YOU CAN FIND |
| ENGINEERING STANDARD DETAILS FROM WPB WEBSITE-POLLUTION |
| CONTROL |
| HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS |
| /FORMS,-PERMITS-APPLICATIONS |
| -ADD DETAIL OF SILT FENCE AND WHERE TO INSTALL IT. |
| |
| 2. [FBC R403.1.7.3] FOUNDATION ELEVATION. |
| ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION |
| SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER |
| AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED |
| DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 |
| PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO |
| THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN |
| BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF |
| DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT |
| ALL LOCATIONS ON THE SITE. |
| -PROVIDE DRAINAGE PLAN OR ADD DRAINAGE DETAILS TO SITE |
| PLAN. SHOW ELEVATION CANGES AND HOW WATER IS MAINTAINED |
| ON SITE AND DEPOSITED TO STREET DRAIN. |
| |
| 3. [FBC 107.2.5]PROVIDE SURVEY OF PROPERTY SHOWING |
| EASEMENTS. |
| [FL. STATUTE 472]SURVEY TO BE SIGNED AND SEALED BY THE |
| SURVEYOR OF RECORD. |
| |
| 4. [FBC R807] THE ROUGH-FRAMED OPENING SHALL BE NOT |
| LESS THAN 22 INCHES |
| BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE LOCATED IN |
| A |
| HALLWAY OR OTHER READILY ACCESSIBLE LOCATION. WHERE |
| LOCATED IN |
| A WALL, THE OPENING SHALL BE NOT LESS THAN 22 INCHES |
| WIDE BY |
| 30 INCHES HIGH (559 MM WIDE BY 762 MM HIGH). WHERE THE |
| ACCESS IS LOCATED IN A CEILING, MINIMUM UNOBSTRUCTED |
| HEADROOM |
| IN THE ATTIC SPACE SHALL BE 30 INCHES (762 MM) AT SOME |
| POINT ABOVE THE ACCESS MEASURED VERTICALLY FROM THE |
| BOTTOM |
| OF CEILING FRAMING MEMBERS. |
| |
| 5. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVAL, |
| ATTACHMENT AND INSTALLATION INSTRUCTIONS FOR HARDIE |
| BOARD OVER MASONRY. |
| THERE IS NO DIRECT ATTACHMENT OF HARDIE SIDING TO |
| MASONRY, SO PLEASE PROVIDE DETAIL OF |
| FURRING/ATTACHMENT, BARRIER AND SIDING ATTACHMENT. |
| |
| 6. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR |
| ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFERED. |
| |
| 7. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS TO |
| THE BUILDING INSPECTOR PRIOR TO INSTALLATION.(THIS WILL |
| BE A PROVISO) |
| |
| 8. [FBC ENERGY R401.3]PROVIDE ENERGY PERFORMANCE LEVEL |
| (EPL)DISPLAY CARD WITH THE ENEGRY CALCULATIONS TO SHOW |
| ESTIMATED ENERGY PERFORMANCE LEVEL. THIS CARD IS TO BE |
| AVAILABLE FOR INSPECTOR TO REVIEW FOR BUILDING FINAL. |
| ALSO, INCLUDE CHECKLISTS WITH ENERGY CALCULATIONS. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |