Plan Review Notes
Plan Review Notes For Permit 18100052
Permit Number 18100052
Review Stop M
Sequence Number 1
Notes
Date Text
2018-10-11 13:19:231ST REVIEW FBC-2017 MECHANICAL
 REVISION #18100052
 10/12/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED MARKED UP PLAN IS NOT ACCEPTABLE PER
 SECTION 107.2.1 WPB. THE ARCHITECT OF RECORD SHALL
 PROVIDE A SIGNED AND SEALED REVISED PLAN SHEET WITH
 CLOUDS AND SYMBOLS TO INDICATE ALL CHANGES MADE TO THE
 APPROVED MECHANICAL PLAN- SEE SECTION 61G1-16.0003 FAC.
  
 2) PLEASE NOTE THAT MISSING FROM THE MARKED UP PLAN
 SHEET ARE THE DUCT SMOKE DETECTORS AND MOTORIZED
 DAMPERS FOR O/A INTAKE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  