Plan Review Notes For Permit 18100052 |
Permit Number |
18100052 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-11 13:19:23 | 1ST REVIEW FBC-2017 MECHANICAL | | REVISION #18100052 | | 10/12/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE SUBMITTED MARKED UP PLAN IS NOT ACCEPTABLE PER | | SECTION 107.2.1 WPB. THE ARCHITECT OF RECORD SHALL | | PROVIDE A SIGNED AND SEALED REVISED PLAN SHEET WITH | | CLOUDS AND SYMBOLS TO INDICATE ALL CHANGES MADE TO THE | | APPROVED MECHANICAL PLAN- SEE SECTION 61G1-16.0003 FAC. | | | | 2) PLEASE NOTE THAT MISSING FROM THE MARKED UP PLAN | | SHEET ARE THE DUCT SMOKE DETECTORS AND MOTORIZED | | DAMPERS FOR O/A INTAKE. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|