Review Stop E
Sequence Number 1
Notes
Date Text
2018-10-04 09:48:27FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-2
  
 RISER SHOW 1/0 AL WITH 150A MAIN, CONDUCTORS ARE ONLY
 GOOD FOR 125A PER CODE. 310.15(B)(16).
  
 #8 FEEDING THE 60A BREAKER ?
  
 YOUR CALCULATION SHOWS THE #8 AT 75 AMPERES?
 310.15(B)(16) SHOWS 55 AMPERES?
  
  
  
  