2018-11-27 09:22:222ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18091335
 11/27/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO COMMENT #1 FROM THE 1ST REVIEW WHICH
 IS PRINTED BELOW, THE ENGINEER IS STATING IN HIS
 REPONSE LETTER THAT RETURN AIR GOES THROUGH THE EDGES
 OF THE EXISTING LIGHT FIXTURES. PLEASE SEE SHEETS E-2,
 E-4, AND E-6: SOME OF THE EXISTING LIGHT FIXTURES IN
 THE OFFICES ARE BEING REPLACED WITH NEW 2X4 COLUMBIA
 LCA24 TROFFERS. THE PRODUCT CUT SHEETS FOR THESE
 FIXTURES DO NOT SHOW OPEN EDGES FOR RETURN AIR.
  
 2) THE ADDRESS ON THE PERMIT APPLICATION DOES NOT MATCH
 THE ADDRESS ON THE PLANS- PLEASE CORRECT.
  
 1) M-2: THE PLANS DO NOT CLEARLY SHOW HOW ALL OF THE
 SUPPLY AIR SHOWN IN THE LARGE 5TH FLOOR PLAN WILL BE
 RETURNED INTO THE PLENUM. PLEASE SHOW THE LOCATIONS AND
 SIZES OF ALL RETURN GRILLS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  