2018-10-10 15:57:12****CORRECTIONS****
 W.P.B. PERMIT: 18091331
 REVIEWED: OCTOBER 10, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 1. [FBC AMENDED 107.2.5] PROVIDE PLAN AND ELEVATION
 VIEW TO SHOW LOCATION AND SIZE OF EXISTING STOREFRONT
 AND NEW STOREFRONT.
  
 2. [FBC AMENDED 107.2.5] IS THIS DOOR FIRE RATED?
 EGRESS? WHAT IS THE EXISTING HARDWARE AND WHAT IS THE
 NEW?
  
 3. [FBC ENERGY C401.2] WHERE SOME OR ALL OF AN EXISTING
 FENESTRATION UNIT IS REPLACED WITH A NEW FENESTRATION
 PRODUCT, INCLUDING SASH AND GLAZING, THE REPLACEMENT
 FENESTRATION UNIT SHALL MEET THE APPLICABLE
 REQUIREMENTS FOR U-FACTOR AND SHGC IN TABLE C402.4
 (SEE C401.2.1 FOR EXCEPTION FOR COMBINING AREA WEIGHTED
 AVERAGE)
 WHAT ARE THE SHGC AND U-FACTOR OF REPLACEMENT GLAZING?
  
 4. [FBC 1609.1.1]PROVIDE DESIGN DATA TO MEET WIND
 REQUIREMENTS.
 OCCUPANCY = ___
 TYPE OF WALL CONSTRUCTION = _________(ARE THE WALLS
 MASONRY, CONCRETE OR WOOD FRAMED?)
 METHOD OF DESIGN = (ASCE 7-10?)
 RISK CATEGORY = ___(II?)
 EXPOSURE CATEGORY = ___(B,C OR D?)
 BUILDING CLASSIFICATION = __________(ENCLOSED?)
 MEAN BLDG. HGT. = ___FT. ___IN.
 WIND SPEED V ULT = _____(170?)
 WIND SPEED V ASD = _____(132?)
 ZONE OF OPENING = (4 OR 5?)
 DESIGN PRESSURE = +___ & -___
  
 5. [FBC 1609.1.2]PROTECTION OF OPENINGS
 PLEASE PROVIDE PRODUCT APPROVAL FOR IMPACT PROTECTION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  