2018-10-10 15:57:12 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18091331 |
| REVIEWED: OCTOBER 10, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC ENERGY = FBC ENERGY CONSERVATION |
| |
| 1. [FBC AMENDED 107.2.5] PROVIDE PLAN AND ELEVATION |
| VIEW TO SHOW LOCATION AND SIZE OF EXISTING STOREFRONT |
| AND NEW STOREFRONT. |
| |
| 2. [FBC AMENDED 107.2.5] IS THIS DOOR FIRE RATED? |
| EGRESS? WHAT IS THE EXISTING HARDWARE AND WHAT IS THE |
| NEW? |
| |
| 3. [FBC ENERGY C401.2] WHERE SOME OR ALL OF AN EXISTING |
| FENESTRATION UNIT IS REPLACED WITH A NEW FENESTRATION |
| PRODUCT, INCLUDING SASH AND GLAZING, THE REPLACEMENT |
| FENESTRATION UNIT SHALL MEET THE APPLICABLE |
| REQUIREMENTS FOR U-FACTOR AND SHGC IN TABLE C402.4 |
| (SEE C401.2.1 FOR EXCEPTION FOR COMBINING AREA WEIGHTED |
| AVERAGE) |
| WHAT ARE THE SHGC AND U-FACTOR OF REPLACEMENT GLAZING? |
| |
| 4. [FBC 1609.1.1]PROVIDE DESIGN DATA TO MEET WIND |
| REQUIREMENTS. |
| OCCUPANCY = ___ |
| TYPE OF WALL CONSTRUCTION = _________(ARE THE WALLS |
| MASONRY, CONCRETE OR WOOD FRAMED?) |
| METHOD OF DESIGN = (ASCE 7-10?) |
| RISK CATEGORY = ___(II?) |
| EXPOSURE CATEGORY = ___(B,C OR D?) |
| BUILDING CLASSIFICATION = __________(ENCLOSED?) |
| MEAN BLDG. HGT. = ___FT. ___IN. |
| WIND SPEED V ULT = _____(170?) |
| WIND SPEED V ASD = _____(132?) |
| ZONE OF OPENING = (4 OR 5?) |
| DESIGN PRESSURE = +___ & -___ |
| |
| 5. [FBC 1609.1.2]PROTECTION OF OPENINGS |
| PLEASE PROVIDE PRODUCT APPROVAL FOR IMPACT PROTECTION. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |