Plan Review Notes
Plan Review Notes For Permit 18091312
Permit Number 18091312
Review Stop E
Sequence Number 3
Notes
Date Text
2018-12-21 13:06:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.
 SERVICE LOAD FOR THIS PROJECT AND FOR ENTIRE SERVICE,
 AND SIZE OF EXISTING SERVICE MUST BE CONFIRMED FOR
 APPROVAL.)(3RD REVIEW: THE TOTAL LOAD CALCULATION FOR
 THE SERVICE HAS NOT BEEN PROVIDED. THIS PROJECT AND THE
 LOAD CALCULATION ON PLAN ARE FOR 539 CLEMATIS. HOWEVER,
 THE SERVICE FEEDERS ALSO FEED 537 CLEMATIS, AND A LOAD
 CALCULATION INCLUDING THOSE LOADS MUST BE PROVIDED. IN
 REFERENCE TO THE LOAD CALCULATION FOR THIS PROJECT,
 PANEL PP1 SHOWS A DEMAND FACTOR OF 80% FOR AC
 EQUIPMENT. PROVIDE CODE SECTION THAT PERMITS THIS
 REDUCTION IN LOAD, OR CORRECT LOAD CALCULATION TO
 INCLUDE 125% OF THE CONTINUOUS LOAD AND 100% OF THE
 NON-CONTINUOUS LOAD PER CODE. ADDITIONALLY, RISER
 DIAGRAM SHOWS PANEL RP-B BEING FED FROM PANEL RP-A.
 HOWEVER, THERE IS NO LOAD SHOWN IN PANEL RP-A FOR PANEL
 RP-B. THERE IS LOAD SHOWN FOR PANEL RP-IG, BUT THE
 RISER DIAGRAM SHOWS THIS FED FROM GUTTER. CLARIFY
 AND/OR CORRECT.)
 9. CORRECTED.
 10. PROVIDE CORRECTED RISER DIAGRAM, SHOWING ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. RISER PROVIDED
 DOES NOT SHOW WIRE SIZES TO MAIN AND GUTTER AND DOES
 NOT SHOW SIZE OF MAIN. PROVIDE CORRECTION. NEC 215.5,
 230, 250.50, 250.94, 408.30 (NOT PROVIDED, REQUIRED FOR
 APPROVAL.)(3RD REVIEW: IN ADDITION TO THE ITEMS
 MENTIONED IN COMMENT 8 ABOVE, THERE NEEDS TO BE FURTHER
 CORRECTIONS TO THE RISER DIAGRAM. AFTER SITE VISIT, I
 SEE THAT THERE IS NOT A "EXISTING SERVICE END BOX" AS
 SHOWN ON PLAN. THE FPL FEED GOES DIRECTLY INTO A LINE
 GUTTER. THERE IS A DISCONNECT AND METER FOR 537
 CLEMATIS MOUNTED AT THE LOCATION OF THIS LINE GUTTER,
 BUT I DID NOT SEE THE 600 AMP MAIN THAT IS STATED IN
 RISER DIAGRAM. WHERE IS THIS MAIN LOCATED? IS IT INSIDE
 THE ELECTRICAL ROOM AND FEEDS ANOTHER GUTTER? ARE
 PANELS RP-A AND RP-B FED AS A TAP FROM THIS GUTTER, OR
 ARE THERE MAINS AHEAD OF THEM? THE PANELS ARE SHOWN AS
 MAIN LUG ONLY. NEED CLARIFICATION AND/OR CORRECTION.)
 11. AIC DEFERRED SUBMITTAL ACCEPTED.
 12. CORRECTED.
 13. CORRECTED.
  
 NEW COMMENT:
  
 14. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW
 IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
 THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE
 $20,530.32.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER