2018-12-21 13:06:39 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. CORRECTED. |
| 2. CORRECTED. |
| 3. CORRECTED. |
| 4. CORRECTED. |
| 5. CORRECTED. |
| 6. CORRECTED. |
| 7. CORRECTED. |
| 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED. |
| SERVICE LOAD FOR THIS PROJECT AND FOR ENTIRE SERVICE, |
| AND SIZE OF EXISTING SERVICE MUST BE CONFIRMED FOR |
| APPROVAL.)(3RD REVIEW: THE TOTAL LOAD CALCULATION FOR |
| THE SERVICE HAS NOT BEEN PROVIDED. THIS PROJECT AND THE |
| LOAD CALCULATION ON PLAN ARE FOR 539 CLEMATIS. HOWEVER, |
| THE SERVICE FEEDERS ALSO FEED 537 CLEMATIS, AND A LOAD |
| CALCULATION INCLUDING THOSE LOADS MUST BE PROVIDED. IN |
| REFERENCE TO THE LOAD CALCULATION FOR THIS PROJECT, |
| PANEL PP1 SHOWS A DEMAND FACTOR OF 80% FOR AC |
| EQUIPMENT. PROVIDE CODE SECTION THAT PERMITS THIS |
| REDUCTION IN LOAD, OR CORRECT LOAD CALCULATION TO |
| INCLUDE 125% OF THE CONTINUOUS LOAD AND 100% OF THE |
| NON-CONTINUOUS LOAD PER CODE. ADDITIONALLY, RISER |
| DIAGRAM SHOWS PANEL RP-B BEING FED FROM PANEL RP-A. |
| HOWEVER, THERE IS NO LOAD SHOWN IN PANEL RP-A FOR PANEL |
| RP-B. THERE IS LOAD SHOWN FOR PANEL RP-IG, BUT THE |
| RISER DIAGRAM SHOWS THIS FED FROM GUTTER. CLARIFY |
| AND/OR CORRECT.) |
| 9. CORRECTED. |
| 10. PROVIDE CORRECTED RISER DIAGRAM, SHOWING ALL |
| DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD |
| SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO |
| ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. RISER PROVIDED |
| DOES NOT SHOW WIRE SIZES TO MAIN AND GUTTER AND DOES |
| NOT SHOW SIZE OF MAIN. PROVIDE CORRECTION. NEC 215.5, |
| 230, 250.50, 250.94, 408.30 (NOT PROVIDED, REQUIRED FOR |
| APPROVAL.)(3RD REVIEW: IN ADDITION TO THE ITEMS |
| MENTIONED IN COMMENT 8 ABOVE, THERE NEEDS TO BE FURTHER |
| CORRECTIONS TO THE RISER DIAGRAM. AFTER SITE VISIT, I |
| SEE THAT THERE IS NOT A "EXISTING SERVICE END BOX" AS |
| SHOWN ON PLAN. THE FPL FEED GOES DIRECTLY INTO A LINE |
| GUTTER. THERE IS A DISCONNECT AND METER FOR 537 |
| CLEMATIS MOUNTED AT THE LOCATION OF THIS LINE GUTTER, |
| BUT I DID NOT SEE THE 600 AMP MAIN THAT IS STATED IN |
| RISER DIAGRAM. WHERE IS THIS MAIN LOCATED? IS IT INSIDE |
| THE ELECTRICAL ROOM AND FEEDS ANOTHER GUTTER? ARE |
| PANELS RP-A AND RP-B FED AS A TAP FROM THIS GUTTER, OR |
| ARE THERE MAINS AHEAD OF THEM? THE PANELS ARE SHOWN AS |
| MAIN LUG ONLY. NEED CLARIFICATION AND/OR CORRECTION.) |
| 11. AIC DEFERRED SUBMITTAL ACCEPTED. |
| 12. CORRECTED. |
| 13. CORRECTED. |
| |
| NEW COMMENT: |
| |
| 14. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE |
| NOT BEEN ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT |
| REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN |
| AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW |
| IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO |
| EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A |
| LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B) |
| THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE |
| $20,530.32. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |