Plan Review Notes
Plan Review Notes For Permit 18091312
Permit Number 18091312
Review Stop P
Sequence Number 2
Notes
Date Text
2018-12-13 09:20:07PROVISO:
 1. PROVIDE FIRE STOPPING SPECIFICATIONS FOR FLOOR
 PENETRATIONS OF PVC AND METALLIC PIPING. PER WPB AMEND
 TO FBC 107.2.1
 2. PROVIDE FIRE STOPPING SPECIFICATIONS FOR WALL
 PENETRATIONS OF PVC PIPING. PER WPB AMEND TO FBC
 107.2.1
 3. PROVIDE DETAILS FOR SWAY BRACING PER FBC PL 308.6
 SWAY BRACING.RIGID SUPPORT SWAY BRACING SHALL BE
 PROVIDED AT CHANGES IN DIRECTION GREATER THAN 45
 DEGREES FOR PIPE SIZES 4 INCHES AND LARGER.
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  