2018-12-06 16:50:441ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18091312
 12/6/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) M101 & M102: SHOW THE LOCATIONS OF ACCESS PANELS FOR
 SERVICE AND REPLACEMENT OF ANY VAV BOXES LOCATED ABOVE
 HARD CEILINGS- SECTION 306.1 FBC M. PLEASE INCLUDE THE
 DIMENSIONS OF THE PANELS
  
 2) SHEET S103 & M103: A) THE TYP. MECH.UNIT ATTACHMENT
 DETAIL IS MISSING THE RTU ATTACHMENT TO THE 12 GA.
 ANGLE. B) EXHAUST FAN CURB ATTACHMENT DETAIL MISSING
 FAN TO CURB ATTACHMENT. IF THE FAN HAS FLORIDA PRODUCT
 OR MIAMI-DADE NOA APPROVAL, PLEASE PROVIDE THE
 DOCUMENT. C) ENGINEERING FOR INSTALLATION OF THE
 ROOFTOP DUCTWORK NOT PROVIDED. PROVIDE DETAILS
 INDICATING HOW THE DUCTWORK WILL BE SUPPORTED AND
 ATTACHED TO THE ROOF STRUCTURE. D) STEEL DUNNAGE
 ATTACHMENT TO THE ROOF STRUCTURE NOT PROVIDED.
  
 3) M103: INDICATE THE TYPE AND GAGE OF ROOFTOP DUCTWORK
 TO BE INSTALLED, AND THE INSULATION R-VALUE.
  
 4) EN-001: THE COMCHECK COMPLIANCE REPORT IS MISSING
 THE DATA FOR THE AC-3 & 4 MITSUBISHI SYSTEMS.
  
 5) THE SUMMARY AC CALCULATIONS UPLOADED ARE MISSING THE
 PROJECT ADDRESS, THE OUTDOOR WET AND DRY BULB
 TEMPERATURES USED, AND THE INDOOR DRY BULB TEMPERATURE
 USED.
  
  
 ]WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  