Date |
Text |
2018-12-06 09:05:03 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. CORRECTED. |
| 2. CORRECTED. |
| 3. CORRECTED. |
| 4. CORRECTED. |
| 5. CORRECTED. |
| 6. CORRECTED. |
| 7. CORRECTED. |
| 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED. |
| SERVICE LOAD FOR THIS PROJECT AND FOR ENTIRE SERVICE, |
| AND SIZE OF EXISTING SERVICE MUST BE CONFIRMED FOR |
| APPROVAL.) |
| 9. CORRECTED. |
| 10. PROVIDE CORRECTED RISER DIAGRAM, SHOWING ALL |
| DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD |
| SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO |
| ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. RISER PROVIDED |
| DOES NOT SHOW WIRE SIZES TO MAIN AND GUTTER AND DOES |
| NOT SHOW SIZE OF MAIN. PROVIDE CORRECTION. NEC 215.5, |
| 230, 250.50, 250.94, 408.30 (NOT PROVIDED, REQUIRED FOR |
| APPROVAL.) |
| 11. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 (NOT PROVIDED, REQUIRED FOR APPROVAL. |
| A DEFERRED SUBMITTAL IS ACCEPTABLE IF RESPONSE FROM FPL |
| IS DELAYED. HOWEVER, BE ADVISED THAT THE CONTRACTOR IS |
| PROCEEDING AT HIS OWN RISK. IF THIS IS DESIRED, PROVIDE |
| BLOCK NOTE ON PLAN THAT THIS INFORMATION WILL BE |
| PROVIDED PRIOR TO FIRST INSPECTION.) |
| 12. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND |
| PANELS. NEC 110.3, 110.9 (NOT PROVIDED, REQUIRED FOR |
| APPROVAL. A DEFERRED SUBMITTAL IS ACCEPTABLE IF |
| RESPONSE FROM FPL IS DELAYED. HOWEVER, BE ADVISED THAT |
| THE CONTRACTOR IS PROCEEDING AT HIS OWN RISK. IF THIS |
| IS DESIRED, PROVIDE BLOCK NOTE ON PLAN THAT THIS |
| INFORMATION WILL BE PROVIDED PRIOR TO FIRST |
| INSPECTION.) |
| 13. CORRECTED. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |