2018-12-06 09:05:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.
 SERVICE LOAD FOR THIS PROJECT AND FOR ENTIRE SERVICE,
 AND SIZE OF EXISTING SERVICE MUST BE CONFIRMED FOR
 APPROVAL.)
 9. CORRECTED.
 10. PROVIDE CORRECTED RISER DIAGRAM, SHOWING ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. RISER PROVIDED
 DOES NOT SHOW WIRE SIZES TO MAIN AND GUTTER AND DOES
 NOT SHOW SIZE OF MAIN. PROVIDE CORRECTION. NEC 215.5,
 230, 250.50, 250.94, 408.30 (NOT PROVIDED, REQUIRED FOR
 APPROVAL.)
 11. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10 (NOT PROVIDED, REQUIRED FOR APPROVAL.
 A DEFERRED SUBMITTAL IS ACCEPTABLE IF RESPONSE FROM FPL
 IS DELAYED. HOWEVER, BE ADVISED THAT THE CONTRACTOR IS
 PROCEEDING AT HIS OWN RISK. IF THIS IS DESIRED, PROVIDE
 BLOCK NOTE ON PLAN THAT THIS INFORMATION WILL BE
 PROVIDED PRIOR TO FIRST INSPECTION.)
 12. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9 (NOT PROVIDED, REQUIRED FOR
 APPROVAL. A DEFERRED SUBMITTAL IS ACCEPTABLE IF
 RESPONSE FROM FPL IS DELAYED. HOWEVER, BE ADVISED THAT
 THE CONTRACTOR IS PROCEEDING AT HIS OWN RISK. IF THIS
 IS DESIRED, PROVIDE BLOCK NOTE ON PLAN THAT THIS
 INFORMATION WILL BE PROVIDED PRIOR TO FIRST
 INSPECTION.)
 13. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  