2018-11-01 17:22:38 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT SHALL |
| CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, WHICH MUST BE |
| AT LEAST 19 INCHES WIDE BY 17 INCHES DEEP, NOMINAL |
| SIZE, AND WALL-MOUNTED. THE LAVATORY SHALL BE MOUNTED |
| SO AS NOT TO OVERLAP THE CLEAR FLOOR SPACE AREAS |
| REQUIRED BY SECTION 604 FOR THE WHEELCHAIR ACCESSIBLE |
| TOILET COMPARTMENT AND SHALL COMPLY WITH SECTION 606. |
| SUCH LAVATORIES SHALL BE COUNTED AS PART OF THE |
| REQUIRED FIXTURE COUNT FOR THE BUILDING. SEE ALSO |
| SECTION 213.3.4. PER FBC ACC 604.8.1.6 |
| |
| 2. SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE WALL.THE |
| SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, |
| LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND |
| EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. |
| |
| 3. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS.TOILET |
| PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7 |
| INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE |
| WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR. |
| |
| 4. PROVIDE AN ENLARGE DETAIL OF BATHROOMS AND SHOW THE |
| REQUIRED CLEAR FLOOR SPACE FOR THE TOILET AND THE |
| LAVATORY PLEASE INCLUDE THE DIMENSIONS ON THE CLEAR |
| FLOOR SPACES. PER FBC ACC 604.8.1.1 , 606.2 |
| |
| 5. PROVIDE UL APPROVED DETAILS FOR THE FIRE STOPPING ON |
| ALL THE PIPES. PER WPB AMEND TO FBC 107.2.1 |
| |
| 6. SHT. P-801.00 THE TEXT IS NOT LEGIBLE I CAN NOT |
| DETERMINE CODE COMPLIANCE ALL SHEETS SHALL COMPLY WITH |
| WPB AMEND TO FBC 107.2.1.3 |
| |
| 7. THE VENTS ON THE WATER CLOSETS ARE NOT CODE |
| COMPLIANT DRY VENTS SHALL NOT RUN HORIZONTAL BELOW THE |
| FLOOD LEVEL RIM OF THE FIXTURES THEY SHALL COMPLY WITH |
| FBC PL 905.3 , 905.4 |
| |
| 8. PLEASE ENLARGE WATER AND SANITARY ISOMETRIC DRAWING |
| THEY SHALL COMPLY WITH WPB AMEND TO FBC 107.2.1.3 |
| |
| 9. FBC PL 416.5 TEMPERED WATER SHALL BE DELIVERED FROM |
| LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC |
| TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3. |
| THE NOTE ON THE WATER HEATER DETAIL STATE 140- 120 DEG. |
| DOES NOT COMPLY FOR THE LAVATORIES IN THE BATHROOMS. |
| TEMPERED WATER. WATER HAVING A TEMPERATURE RANGE |
| BETWEEN 85?F (29?C) AND 110?F (43?C). UNDER 110 DEG. |
| |
| 10. PLEASE PROVIDE MANUFACTURE SIZING FOR THE 1GAL |
| WATER HEATER CAN SUPPLY THE REQUIRED TEMPERATURE WATER |
| FOR 2 LAVATORIES THE BREAK ROOM SINK AND A SERVICE SINK |
| SIMULTANEOUSLY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 11. PROVIDE MANUFACTURE SPEC FOR URINAL FLUSHVALVE SHOW |
| THAT 1/2" SUPPLY PIPING IS ADEQUATE AS SHOWN ON THE |
| WATER ISOMETRIC DRAWING. PER WPB AMEND TO FBC 107.2.1 |
| |
| 12. SHT. P001 ON THE MAXIMUM FLOW RATE TABLE IT LIST |
| THE MIAMI DADE CODE AND RESIDENTIAL THE PROJECT SHALL |
| BE DESIGNED AND BUILT UNDER THE FBC PL AND FBC ACC 2017 |
| 6TH EDITION PLEASE SHOW ON PLAN. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |