Plan Review Notes
Plan Review Notes For Permit 18091312
Permit Number 18091312
Review Stop M
Sequence Number 1
Notes
Date Text
2018-10-24 17:45:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18091312
 10/24/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 2) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 3) PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR
 THE O/A INTAKE DUCTS- SECTION C403.2.4.3 FBC-17 ENERGY
 CONSERVATION.
  
 4) SHEET M-501.00: PROVIDE DUCT HANGING AND CONNECTION
 DETAILS PER SMACNA HVAC DUCT CONSTRUCTION
 STANDARDS-2005. THE DUCT DETAILS AND HANGER TABLE SHOWN
 ON THE PLANS ARE NOT IN COMPLIANCE, AND ARE BASED ON A
 NYC CODE.
  
 5) M501: PROVIDE A HORIZONTAL FIRE DAMPER INSTALLATION
 DETAIL PER MANUFACTURER'S SPECIFICATIONS AND SUBMIT THE
 SPECS FOR THE DEVICE- SECTION 607.5.2 FBC M. INDICATE
 HOW ACCESS WILL BE PROVIDED TO THE DAMPERS IN THE
 SUPPLY AND RETURN RISERS- SECTION 607.4 FBC M.
  
 6) M101: REQUIRED RETURN AIR FROM THE SECURITY- IT ROOM
 NOT SHOWN.
  
 7) M102: REQUIRED RETURN AIR FROM THE BREAKROOM NOT
 SHOWN.
  
 8) M102: CLARIFY IF ANY COOKING APPLIANCES OR EXHAUST
 HOOD SYSTEMS WILL BE INSTALLED IN THE BREAKROOM OR
 STAFF LOUNGE, AND PROVIDE DETAILS, SPECIFICATIONS, AND
 PRODUCT SUBMITTALS IF APPLICABLE. PLEASE NOTE THAT
 SEPARATE PERMITS ARE REQUIRED FOR KITCHEN EXHAUST HOODS
 AND FIR SUPPRESSION SYSTEMS.
  
 9) M102: THE CONDENSATE DRAINING INTO THE MOP SINK IS
 PROHIBITED PER SECTION 90-126 WPB CODE OF ORDINANCES
  
 10) M103: COMPLETE WIND LOAD ENGINEERING IS REQUIRED
 FOR THE RTU'S, ROOFTOP CONDENSER UNITS AND STANDS, AND
 THE EXHAUST FAN AND CURB- SECTION 301.15. PLEASE NOTE
 THE RTU DETAIL ON S-400 IS INCOMPLETE- RTU ATTACHMENT
 TO CURB NOT SHOWN AND NO DESIGN CRITERIA HAS BEEN
 PROVIDED.
  
 11) M103: SHOW HOW ACCESS IS BEING PROVIDED TO THE
 EQUIPMENT ON THE ROOF- SEE SECTION 306.5 FBC M.
  
 12) M103: VERIFY THE REQUIRED 10' REQUIRED CLEARANCE
 FOR THE SERVICEABLE ROOF TOP MECHANICAL EQUIPMENT TO
 THE ROOF EDGES OR VERIFY 42" GUARD OR PARAPET IN PLACE-
 SECTION 304.11 FBC M.
  
 13) THE PROPOSED PROJECT IS CLASSIFED AS A"RENOVATED
 BUILDING" PER SECTION 202 FBC EC. PLEASE SUBMIT AN
 ENERGY COM[PLIANCE REPORT IN ACCORDANCE WITH SECTIONS
 C101.5.1 & C101.5.1.1 FBC EC.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER