2018-10-24 17:45:55 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18091312 |
| 10/24/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. |
| |
| 2) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE |
| AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL. |
| PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| PROVIDED CFMS OF OUTDOOR AIR. |
| |
| 3) PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR |
| THE O/A INTAKE DUCTS- SECTION C403.2.4.3 FBC-17 ENERGY |
| CONSERVATION. |
| |
| 4) SHEET M-501.00: PROVIDE DUCT HANGING AND CONNECTION |
| DETAILS PER SMACNA HVAC DUCT CONSTRUCTION |
| STANDARDS-2005. THE DUCT DETAILS AND HANGER TABLE SHOWN |
| ON THE PLANS ARE NOT IN COMPLIANCE, AND ARE BASED ON A |
| NYC CODE. |
| |
| 5) M501: PROVIDE A HORIZONTAL FIRE DAMPER INSTALLATION |
| DETAIL PER MANUFACTURER'S SPECIFICATIONS AND SUBMIT THE |
| SPECS FOR THE DEVICE- SECTION 607.5.2 FBC M. INDICATE |
| HOW ACCESS WILL BE PROVIDED TO THE DAMPERS IN THE |
| SUPPLY AND RETURN RISERS- SECTION 607.4 FBC M. |
| |
| 6) M101: REQUIRED RETURN AIR FROM THE SECURITY- IT ROOM |
| NOT SHOWN. |
| |
| 7) M102: REQUIRED RETURN AIR FROM THE BREAKROOM NOT |
| SHOWN. |
| |
| 8) M102: CLARIFY IF ANY COOKING APPLIANCES OR EXHAUST |
| HOOD SYSTEMS WILL BE INSTALLED IN THE BREAKROOM OR |
| STAFF LOUNGE, AND PROVIDE DETAILS, SPECIFICATIONS, AND |
| PRODUCT SUBMITTALS IF APPLICABLE. PLEASE NOTE THAT |
| SEPARATE PERMITS ARE REQUIRED FOR KITCHEN EXHAUST HOODS |
| AND FIR SUPPRESSION SYSTEMS. |
| |
| 9) M102: THE CONDENSATE DRAINING INTO THE MOP SINK IS |
| PROHIBITED PER SECTION 90-126 WPB CODE OF ORDINANCES |
| |
| 10) M103: COMPLETE WIND LOAD ENGINEERING IS REQUIRED |
| FOR THE RTU'S, ROOFTOP CONDENSER UNITS AND STANDS, AND |
| THE EXHAUST FAN AND CURB- SECTION 301.15. PLEASE NOTE |
| THE RTU DETAIL ON S-400 IS INCOMPLETE- RTU ATTACHMENT |
| TO CURB NOT SHOWN AND NO DESIGN CRITERIA HAS BEEN |
| PROVIDED. |
| |
| 11) M103: SHOW HOW ACCESS IS BEING PROVIDED TO THE |
| EQUIPMENT ON THE ROOF- SEE SECTION 306.5 FBC M. |
| |
| 12) M103: VERIFY THE REQUIRED 10' REQUIRED CLEARANCE |
| FOR THE SERVICEABLE ROOF TOP MECHANICAL EQUIPMENT TO |
| THE ROOF EDGES OR VERIFY 42" GUARD OR PARAPET IN PLACE- |
| SECTION 304.11 FBC M. |
| |
| 13) THE PROPOSED PROJECT IS CLASSIFED AS A"RENOVATED |
| BUILDING" PER SECTION 202 FBC EC. PLEASE SUBMIT AN |
| ENERGY COM[PLIANCE REPORT IN ACCORDANCE WITH SECTIONS |
| C101.5.1 & C101.5.1.1 FBC EC. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |