2018-10-18 11:56:32 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE |
| OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS IS |
| FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 |
| 2. PROVIDE SHOW WINDOW RECEPTACLE OUTLETS. NEC 210.62 |
| 3. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC |
| 600.5; FBC EC 405.2.4 |
| 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| 5. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE |
| AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL |
| 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE |
| OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR |
| PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, |
| CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE |
| 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR |
| FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC |
| EC C405.6.1 |
| 6. LIGHTING PLAN NOTE 11 ON SHEET E-101 STATE THAT |
| LIGHTING WILL BE FED FROM PANEL RP-1, WHICH IS NOT |
| SHOWN ON RISER DIAGRAM OR IN PANEL SCHEDULES. CORRECT |
| DISCREPANCY. WPB FBC 107.2.1 |
| 7. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR |
| SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE |
| EQUIPMENT PER CODE. NEC 210.63 |
| 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 |
| 9. PROVIDE LOAD CALCULATION FOR PANELS, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| TO PANELS IS ADEQUATE. NEC 215.2, 220, 408.30 |
| 10. PROVIDE CORRECTED RISER DIAGRAM, SHOWING ALL |
| DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD |
| SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO |
| ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. RISER PROVIDED |
| DOES NOT SHOW WIRE SIZES TO MAIN AND GUTTER AND DOES |
| NOT SHOW SIZE OF MAIN. PROVIDE CORRECTION. NEC 215.5, |
| 230, 250.50, 250.94, 408.30 |
| 11. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 12. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND |
| PANELS. NEC 110.3, 110.9 |
| 13. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| 105.1, 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |