2018-11-15 08:07:37****CORRECTIONS****
 W.P.B. PERMIT: 18091312
 REVIEWED: NOVEMBER 14, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 CURRENT CODES:
 ADOPTED DECEMBER 31, 2017
 FLORIDA BUILDING CODE(FBC), 6TH EDITION (2017)
  
 1. [FBC 107.3.5]UPDATE SHEETS LS-101 AND LS102 FOR
 CURRENT DODE EDITIONS.
  
 2. [FBC 107.3.5]THIS SHOULD BE A LEVEL 3 ALTERARTION
 SINCE IT AFFECTS MORE THAN 50% OF THE BUILDING.
 PLEASE UPDATE LS-101 AND LS102 TO STATE LEVEL 3
 ALTERATION.
  
 3. [FBC TABLE 1004.1.2]SHEETS LS-101 AND LS102 SHOW
 FIRST FLOOR OCCUPANT LOAD FOR MERCANTILE AT 30 SQ. FT.
 PER.
 MERCANTILE WOULD BE CALCULATED AT 60 SQ. FT. PER PERSON
 LIKE SHOWN FOR SECOND FLOOR.
 PLEASE REVISE OCCUPANT COUNT TO REFLECT MERCANTILE PER
 TABLE 1004.1.2.
  
 4. [FBC 1015.7]ROOF ACCESS. GUARDS SHALL BE PROVIDED
 WHERE THE ROOF
 HATCH OPENING IS LOCATED WITHIN 10 FEET (3048 MM) OF A
 ROOF
 EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR
 OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE
 FLOOR,
 ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO
 AS TO
 PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN
 DIAMETER.
 VERIFY THAT PARAPET PROVIDES EDGE PROTECTION OR ADD
 RAIL TO MEET FBC 1015.
 -PROVIDE PRODUCT APPROVAL FOR NEW ROOF HATCH.
  
 5. [FBC 1510.10]MECHANICAL UNITS. ROOF MOUNTED
 MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES
 (203
 MM) ABOVE THE ROOF SURFACE.
 PROVIDE DETAIL OF NEW HVAC EQUIPMENT CURBS. STRUCTURAL
 SHEET S-201 SAYS SEE MECHANICAL AND MECHANICAL M-103
 SAYS SEE STRUCTURAL FOR ATTACHMENT.
  
 6. [FBC 107.3.5]SHEET A-801 AND SHEET A-810 ARE
 REVERSED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  