Plan Review Notes
Plan Review Notes For Permit 18091284
Permit Number 18091284
Review Stop MEDGAS
Sequence Number 4
Notes
Date Text
2019-10-04 12:21:59PLUMBING PROVISO : 18091284
  
 MED GAS COMMENTS: SHALL BE COMPLIED WITH PRIOR TO FINAL
 INSPECTION.
  
 1) SHOW THE TERMINATION POINT OF THE VACUUM PUMP VENT
 LINE. THE DISCHARGE SHALL BE A MINIMUM OF 25 FEET FROM
 ANY DOOR, WINDOW, AIR INTAKE, OR OTHER OPENINGS IN
 BUILDINGS. NFPA 99 SEC.5.1.3.7.6.2.
  
 2) THE MEDICAL AIR INTAKE SHALL BE LOCATED A MINIMUM OF
 25 FEET FROM VENTILATING SYSTEM EXHAUSTS, PLUMBING
 VENTS, VACUUM DISCHARGES, OR OTHER AREAS THAT CAN
 COLLECT OTHER NOXIOUS FUMES. NFPA 99 SEC. 5.1.3.6.3.11.
  
 DEFERRED SUBMITTALS. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VACUUM PUMPS AND AIR
 COMPRESSORS, THE MUFFLER/INTAKE AND ALSO FOR THE
 RECEIVERS, DRYERS, AFTERCOOLERS, ETC.IF THEY ARE BEING
 REPLACED WITH NEW. WPB AMEND. TO FBC SEC. 107.3.4.1
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]