Plan Review Notes
Plan Review Notes For Permit 18091284
Permit Number 18091284
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2019-08-20 10:01:508/20/19
  
 A FEW OF THE PEVIOUS FIRE COMMENTS DO NOT APPEAR TO BE
 ADDRESSED.
  
  
  
 1) COMPLIED
  
  
  
 2) PROVISO COMMENT:
  
 SHEET A 575 - THERE ARE INDICATIONS OF CARDER READERS
 AND ACCESS CONTROL WITHIN THE DOOR SCHEDULE.
  
 CARD READER AND ACCESS CONTROL SHALL BE INSTALLED UNDER
 SPEARATE PERMIT AND SHOP DRAWINGS.
  
 ALL DEVICES AND EQUIPMENT FOR CARD READERS AND ACCESS
 CONTRAL SHALL FUNCTION/OPERATE UNDER THE REQUIREMENTS
 OF NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
  
  
 3) COMPLIED
  
  
  
 4) COMPLIED
  
  
 5) PROVISO COMMENT:
  
 SHEET G 410 - THERE IS AN INDICATION OF A TEMPORARY
 AMBULANCE CANOPY. THERE IS NO DETAIL PLAN SHEET OR
 CALL-OUT DRAWING.
  
 IF THIS A TENT STRUCTURE, IS THE FABRIC FIRE RETARDENT,
 SIZE, HEIGHT, SIDES, LIGHTING, ETC.?
  
 ANY TEMPORAY TENT STRUCTURE SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS THAT INCLUDE, THE
 ABOVE.
  
  
  
 6) PROVISO COMMENT:
  
 SHEET G 410 - A CONSTRUCTION BARRIER IS INDICATED.
 THERE IS NO DETAIL PLAN SHEET OR CALL-OUT DRAWING.
  
 WILL THIS AREA BE CONSTRUCTION MATERIAL, HAVE LIGHTING,
 EXIT SIGNAGE, SIDES, SPRINKLER PROTECTION, FIRE ALARM
 DEVICES, ETC.
  
 SHOP DRAWINGS REQUIRED
  
  
  
 7) PROVISO COMMENT:
  
 SHEET G 410 - A TEMPORARY PUB ED CANOPY IS INDICATED.
 WHAT IS THE PURPOSE AND OCCUPANCY CLASSIFICATION OF
 THIS CANOPY?
  
 EDUCATION CLASSROOM, ASEEMBLY GATHERING AREA,? HOW WILL
 IT BE CONSTRUCTED? IS IT TEMPORARY TENT WITH SIDES?
  
 ANY TEMPORAY TENT STRUCTURE SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS THAT INCLUDE, THE
 ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]