2019-08-20 10:01:50 | 8/20/19 |
| |
| A FEW OF THE PEVIOUS FIRE COMMENTS DO NOT APPEAR TO BE |
| ADDRESSED. |
| |
| |
| |
| 1) COMPLIED |
| |
| |
| |
| 2) PROVISO COMMENT: |
| |
| SHEET A 575 - THERE ARE INDICATIONS OF CARDER READERS |
| AND ACCESS CONTROL WITHIN THE DOOR SCHEDULE. |
| |
| CARD READER AND ACCESS CONTROL SHALL BE INSTALLED UNDER |
| SPEARATE PERMIT AND SHOP DRAWINGS. |
| |
| ALL DEVICES AND EQUIPMENT FOR CARD READERS AND ACCESS |
| CONTRAL SHALL FUNCTION/OPERATE UNDER THE REQUIREMENTS |
| OF NFPA 101, CHAPTER 7, MEANS OF EGRESS. |
| |
| |
| |
| 3) COMPLIED |
| |
| |
| |
| 4) COMPLIED |
| |
| |
| 5) PROVISO COMMENT: |
| |
| SHEET G 410 - THERE IS AN INDICATION OF A TEMPORARY |
| AMBULANCE CANOPY. THERE IS NO DETAIL PLAN SHEET OR |
| CALL-OUT DRAWING. |
| |
| IF THIS A TENT STRUCTURE, IS THE FABRIC FIRE RETARDENT, |
| SIZE, HEIGHT, SIDES, LIGHTING, ETC.? |
| |
| ANY TEMPORAY TENT STRUCTURE SHALL BE INSTALLED UNDER |
| SEPARATE PERMIT AND SHOP DRAWINGS THAT INCLUDE, THE |
| ABOVE. |
| |
| |
| |
| 6) PROVISO COMMENT: |
| |
| SHEET G 410 - A CONSTRUCTION BARRIER IS INDICATED. |
| THERE IS NO DETAIL PLAN SHEET OR CALL-OUT DRAWING. |
| |
| WILL THIS AREA BE CONSTRUCTION MATERIAL, HAVE LIGHTING, |
| EXIT SIGNAGE, SIDES, SPRINKLER PROTECTION, FIRE ALARM |
| DEVICES, ETC. |
| |
| SHOP DRAWINGS REQUIRED |
| |
| |
| |
| 7) PROVISO COMMENT: |
| |
| SHEET G 410 - A TEMPORARY PUB ED CANOPY IS INDICATED. |
| WHAT IS THE PURPOSE AND OCCUPANCY CLASSIFICATION OF |
| THIS CANOPY? |
| |
| EDUCATION CLASSROOM, ASEEMBLY GATHERING AREA,? HOW WILL |
| IT BE CONSTRUCTED? IS IT TEMPORARY TENT WITH SIDES? |
| |
| ANY TEMPORAY TENT STRUCTURE SHALL BE INSTALLED UNDER |
| SEPARATE PERMIT AND SHOP DRAWINGS THAT INCLUDE, THE |
| ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |