Plan Review Notes
Plan Review Notes For Permit 18091284
Permit Number 18091284
Review Stop P
Sequence Number 2
Notes
Date Text
2019-07-14 06:21:041) SHT. G171 - DETAILS #1,2,3 - THERE IS NO APPROVED
 LISTING FOR THESE PENETRATION DETAILS. CLARIFY. AN
 ENGINEERING JUDGEMENT MAY BE REQUIRED FROM UL. 2017 FBC
 SEC. 714.
 2) SHT. G175 - DETAIL #6 - CLARIFY THE LOCATION OF THE
 REQUIRED CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAIN.
 THE CLEAR FLOOR SPACE SHALL COMPLY WITH 2107 FBC SEC.
 602.2 AND BE CENTERED ON THE UNIT.
 3) SHT. A600 - DETAIL #2 - SHOW THE CLEAR INSIDE
 DIMENSIONS (L X W) OF THE ACCESSIBLE SHOWER. TRANSFER
 SHOWERS SHALL BE 36 INCHES BY 36 INCHES AND SHALL
 COMPLY WITH 2017 FBC - ACCESSIBILITY SEC.608.2.
 4) GRAB BARS IN THE TRANSFER SHOWER SHALL COMPLY WITH
 2017 FBC-ACCESSIBILITY SEC. 608.3.1.
 5) A SHOWER SPRAY UNIT SHALL BE PROVIDED IN THE SHOWER
 AND COMPLY WITH 2017 FBC-ACCESS/ SEC.608.6.
 6) THRESHOLD FOR THE SHOWER SHALL COMPLY WITH 2017 FBC
 -ACCESS. SEC.608.7.
 7) THE SEAT IN THE ACCESSIBLE SHOWER SHALL COMPLY WITH
 2017 FBC- ACCESS. SEC. 610.3.2.
 8) SHT.A351 - DETAIL #1 - THE OVERFLOW SCUPPER SHALL BE
 LOCATED NO MORE THAN 4 INCHES ABOVE THE FINISHED ROOF
 COVERING AND SHALL BE LOCATED AS CLOSE AS PRACTICAL TO
 REQUIRED VERTICAL LEADERS OR DOWNSPOUTS PER 2017 FBC
 SEC.1503.4.2.1.
 9) SHT. A600 SHOWS A GRAB BAR IN THE VERTICAL POSITION.
 GRAB BARS ARE NOT PERMITTED TO BE INSTALLED IN A
 VETICAL POSITION PER 2017 FBC-ACCESS. SEC.609.4.
 10) SHT. A600 - TOILET ACCESSORY LEGEND - IDENTIFY ON
 THE GRAB BAR DETAILS WHICH DETAILS APPLY TO THE SIDE
 WALL GRAB BAR AND WHICH ONES APPLY TO THE REAR WALL. IT
 IS CONFUSING . 2017 FBC - ACCESS. SEC.604.5.1 &
 604.5.2.
 11) SHT. A600 - DETAIL # 2 - THE DOOR CANNOT SWING INTO
 THE REQUIRED CLEAR FLOOR SPACE FOR THE LAVATORY AND THE
 SHOWER. 2017 FBC - ACCESS. SEC.603.2.3. SEE EXCEPTION
 #2.
 12) SHT. A652 - DETAIL #4 - SHOW THE MOUNTING HEIGHT OF
 THE LAVATORY IN THE NURSE'S STATION.
 13) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE VACUUM
 PUMPS AND AIR COMPRESSORS, THE MUFFLER/INTAKE AND ALSO
 FOR THE RECEIVERS, DRYERS, AFTERCOOLERS, ETC.IF THEY
 ARE BEING REPLACED WITH NEW. WPB AMEND. TO FBC SEC.
 107.2.1.
 14) THE VACUUM PUMPS SHALL BE PROVIDED WITH
 ANTIVIBRATION MOUNTINGS PERR NFPA 99 SEC.5.1.3.7.2.2.
 15) SHOW THE TERMINATION POINT OF THE VACUUM PUMP VENT
 LINE. THE DISCHARGE SHALL BE A MINIMUM OF 25 FEET FROM
 ANY DOOR, WINDOW, AIR INTAKE, OR OTHER OPENINGS IN
 BUILDINGS. NFPA 99 SEC.5.1.3.7.6.2.
 16) THE MEDICAL AIR INTAKE SHALL BE LOCATED A MINIMUM
 OF 25 FEET FROM VENTILATING SYSTEM EXHAUSTS, PLUMBING
 VENTS, VACUUM DISCHARGES, OR OTHER AREAS THAT CAN
 COLLECT OTHER NOXIOUS FUMES. NFPA 99 SEC. 5.1.3.6.3.11.
 17) MEDICAL AIR DRYERS SHALL BE PROVIDED WITH
 ANTIVIBRATION MOUNTINGS PER NFPA 99 SEC. 5.1.3.6.3.7
 (4).
 18) SHT.P002 - DETAIL # 7 - A PRESSURE INDICATOR(S)
 SHALL BE LOCATED DOWNSTREAM OF EACH REGULATOR OR
 IMMEDIATELY DOWNSTREAM OF THE ISOLATING VALVES FOR THE
 REGULATORS PER NFPA 99 SEC. 5.1.3.5.5.1 (3).
 19) SUBMIT RISER DIAGRAMS FOR ALL THE MEDICAL GAS
 PIPING TO BE INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1.
 20) SHT. P002 - DETAIL #7 - THE PRESSURE RELIEF VALVES
 ON THE COMPRESSED AIR SYSTEM SHALL BE VENTED IN
 ACCORDANCE WITH NFPA 99 SEC. 5.1.3.5.6.1 (4).
 21) IDENTIFY THE CONTINUATION POINTS OF THE MEDICAL GAS
 PIPING ON THE REQUESTED MEDICAL GAS RISER DIAGRAMS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 22) THE AREA(S) HOUSING THE VACUUM PUMP AND AIR
 COMPRESSOR SHALL BE VENTILATED PER NFPA 99
 SECS.5.1.3.3.3.3, 5.1.3.6.3.1, 5.1.3.7.1.1.
 23) THE NEW OUTDOOR ENCLOSURE FOR THE MEDICAL GAS SHALL
 BE VENTILATED PER NFPA 99 SEC.5.1.3.3.3.4 (1).
 24) CLEANOUTS ARRE REQUIRED IN THE BASE OF THE
 STORMWATER RISERS. 2017 FBC-PLUMBING SEC.1101.8.
 25) INDICATE ON THE IRRIGATION PLANS IF THERE IS AN
 EXISTING BACKFLOW PRVENTION DEVICE, RAIN SENSOR AND
 SYSTEM CONTROLLER ON THE SYSTEM.
 26) SHT.P400 - THE WATER RISER DIAGRAM SHOWS WATER
 PIPING LINES WITH NO CONNECTION POINTS. IDENTIFY ALL
 CONNECTION POINTS OF THE WATER PIPING SYSTEM TO THE
 EXISTING SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1.
 27) SHT. P400 - SHOW THE BACKFLOW PREVENTER ON THE THE
 ONE INCH WATER LINE TO THE PENTHOUSE. FBC SEC. 107.2.1.
 28) SHT. P401 - THE RISER DIAGRAM INDICATES FIXTURE
 #503.THIS FIXTURE IS NOT LISTED IN THE PLUMBING FIXTURE
 SCHEDULE. CLARIFY.
 29) THE SANITARY RISER SHOWS SANITARY DRAIN LINES AND
 VENTS WITH NO CONNECTION POINTS. IDENTIFY ALL
 CONNECTION POINTS OF THE SANITARY SSYSTEM TO THE
 EXISTING SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 30) THERE ARE NUMEROUS AREAS ON THE SANITARY RISER THAT
 ARE MISSING PIPE SIZES ON THE VENTS AND HORIZONTAL
 DRAINAGE SYSTEM. ENSURE THAT ALL AREAS OF THE SANITARY
 RISER ARE SIZED AND IN COMPLIANCE WITH THE PLUMBING
 CODE.
 31) PLEASE SUBMIT AN EXPANDED SANITARY RISER DIAGRAM
 FOR REVIEW. THERE ARE AREAS WHERE IT IS EXTREMELY
 DIFFICULT TO DETERMINE IF THE DESIGN IS CODE
 COMPLIANT.WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW