2019-07-14 06:21:04 | 1) SHT. G171 - DETAILS #1,2,3 - THERE IS NO APPROVED |
| LISTING FOR THESE PENETRATION DETAILS. CLARIFY. AN |
| ENGINEERING JUDGEMENT MAY BE REQUIRED FROM UL. 2017 FBC |
| SEC. 714. |
| 2) SHT. G175 - DETAIL #6 - CLARIFY THE LOCATION OF THE |
| REQUIRED CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAIN. |
| THE CLEAR FLOOR SPACE SHALL COMPLY WITH 2107 FBC SEC. |
| 602.2 AND BE CENTERED ON THE UNIT. |
| 3) SHT. A600 - DETAIL #2 - SHOW THE CLEAR INSIDE |
| DIMENSIONS (L X W) OF THE ACCESSIBLE SHOWER. TRANSFER |
| SHOWERS SHALL BE 36 INCHES BY 36 INCHES AND SHALL |
| COMPLY WITH 2017 FBC - ACCESSIBILITY SEC.608.2. |
| 4) GRAB BARS IN THE TRANSFER SHOWER SHALL COMPLY WITH |
| 2017 FBC-ACCESSIBILITY SEC. 608.3.1. |
| 5) A SHOWER SPRAY UNIT SHALL BE PROVIDED IN THE SHOWER |
| AND COMPLY WITH 2017 FBC-ACCESS/ SEC.608.6. |
| 6) THRESHOLD FOR THE SHOWER SHALL COMPLY WITH 2017 FBC |
| -ACCESS. SEC.608.7. |
| 7) THE SEAT IN THE ACCESSIBLE SHOWER SHALL COMPLY WITH |
| 2017 FBC- ACCESS. SEC. 610.3.2. |
| 8) SHT.A351 - DETAIL #1 - THE OVERFLOW SCUPPER SHALL BE |
| LOCATED NO MORE THAN 4 INCHES ABOVE THE FINISHED ROOF |
| COVERING AND SHALL BE LOCATED AS CLOSE AS PRACTICAL TO |
| REQUIRED VERTICAL LEADERS OR DOWNSPOUTS PER 2017 FBC |
| SEC.1503.4.2.1. |
| 9) SHT. A600 SHOWS A GRAB BAR IN THE VERTICAL POSITION. |
| GRAB BARS ARE NOT PERMITTED TO BE INSTALLED IN A |
| VETICAL POSITION PER 2017 FBC-ACCESS. SEC.609.4. |
| 10) SHT. A600 - TOILET ACCESSORY LEGEND - IDENTIFY ON |
| THE GRAB BAR DETAILS WHICH DETAILS APPLY TO THE SIDE |
| WALL GRAB BAR AND WHICH ONES APPLY TO THE REAR WALL. IT |
| IS CONFUSING . 2017 FBC - ACCESS. SEC.604.5.1 & |
| 604.5.2. |
| 11) SHT. A600 - DETAIL # 2 - THE DOOR CANNOT SWING INTO |
| THE REQUIRED CLEAR FLOOR SPACE FOR THE LAVATORY AND THE |
| SHOWER. 2017 FBC - ACCESS. SEC.603.2.3. SEE EXCEPTION |
| #2. |
| 12) SHT. A652 - DETAIL #4 - SHOW THE MOUNTING HEIGHT OF |
| THE LAVATORY IN THE NURSE'S STATION. |
| 13) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE VACUUM |
| PUMPS AND AIR COMPRESSORS, THE MUFFLER/INTAKE AND ALSO |
| FOR THE RECEIVERS, DRYERS, AFTERCOOLERS, ETC.IF THEY |
| ARE BEING REPLACED WITH NEW. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 14) THE VACUUM PUMPS SHALL BE PROVIDED WITH |
| ANTIVIBRATION MOUNTINGS PERR NFPA 99 SEC.5.1.3.7.2.2. |
| 15) SHOW THE TERMINATION POINT OF THE VACUUM PUMP VENT |
| LINE. THE DISCHARGE SHALL BE A MINIMUM OF 25 FEET FROM |
| ANY DOOR, WINDOW, AIR INTAKE, OR OTHER OPENINGS IN |
| BUILDINGS. NFPA 99 SEC.5.1.3.7.6.2. |
| 16) THE MEDICAL AIR INTAKE SHALL BE LOCATED A MINIMUM |
| OF 25 FEET FROM VENTILATING SYSTEM EXHAUSTS, PLUMBING |
| VENTS, VACUUM DISCHARGES, OR OTHER AREAS THAT CAN |
| COLLECT OTHER NOXIOUS FUMES. NFPA 99 SEC. 5.1.3.6.3.11. |
| 17) MEDICAL AIR DRYERS SHALL BE PROVIDED WITH |
| ANTIVIBRATION MOUNTINGS PER NFPA 99 SEC. 5.1.3.6.3.7 |
| (4). |
| 18) SHT.P002 - DETAIL # 7 - A PRESSURE INDICATOR(S) |
| SHALL BE LOCATED DOWNSTREAM OF EACH REGULATOR OR |
| IMMEDIATELY DOWNSTREAM OF THE ISOLATING VALVES FOR THE |
| REGULATORS PER NFPA 99 SEC. 5.1.3.5.5.1 (3). |
| 19) SUBMIT RISER DIAGRAMS FOR ALL THE MEDICAL GAS |
| PIPING TO BE INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1. |
| 20) SHT. P002 - DETAIL #7 - THE PRESSURE RELIEF VALVES |
| ON THE COMPRESSED AIR SYSTEM SHALL BE VENTED IN |
| ACCORDANCE WITH NFPA 99 SEC. 5.1.3.5.6.1 (4). |
| 21) IDENTIFY THE CONTINUATION POINTS OF THE MEDICAL GAS |
| PIPING ON THE REQUESTED MEDICAL GAS RISER DIAGRAMS. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 22) THE AREA(S) HOUSING THE VACUUM PUMP AND AIR |
| COMPRESSOR SHALL BE VENTILATED PER NFPA 99 |
| SECS.5.1.3.3.3.3, 5.1.3.6.3.1, 5.1.3.7.1.1. |
| 23) THE NEW OUTDOOR ENCLOSURE FOR THE MEDICAL GAS SHALL |
| BE VENTILATED PER NFPA 99 SEC.5.1.3.3.3.4 (1). |
| 24) CLEANOUTS ARRE REQUIRED IN THE BASE OF THE |
| STORMWATER RISERS. 2017 FBC-PLUMBING SEC.1101.8. |
| 25) INDICATE ON THE IRRIGATION PLANS IF THERE IS AN |
| EXISTING BACKFLOW PRVENTION DEVICE, RAIN SENSOR AND |
| SYSTEM CONTROLLER ON THE SYSTEM. |
| 26) SHT.P400 - THE WATER RISER DIAGRAM SHOWS WATER |
| PIPING LINES WITH NO CONNECTION POINTS. IDENTIFY ALL |
| CONNECTION POINTS OF THE WATER PIPING SYSTEM TO THE |
| EXISTING SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1. |
| 27) SHT. P400 - SHOW THE BACKFLOW PREVENTER ON THE THE |
| ONE INCH WATER LINE TO THE PENTHOUSE. FBC SEC. 107.2.1. |
| 28) SHT. P401 - THE RISER DIAGRAM INDICATES FIXTURE |
| #503.THIS FIXTURE IS NOT LISTED IN THE PLUMBING FIXTURE |
| SCHEDULE. CLARIFY. |
| 29) THE SANITARY RISER SHOWS SANITARY DRAIN LINES AND |
| VENTS WITH NO CONNECTION POINTS. IDENTIFY ALL |
| CONNECTION POINTS OF THE SANITARY SSYSTEM TO THE |
| EXISTING SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1. |
| 30) THERE ARE NUMEROUS AREAS ON THE SANITARY RISER THAT |
| ARE MISSING PIPE SIZES ON THE VENTS AND HORIZONTAL |
| DRAINAGE SYSTEM. ENSURE THAT ALL AREAS OF THE SANITARY |
| RISER ARE SIZED AND IN COMPLIANCE WITH THE PLUMBING |
| CODE. |
| 31) PLEASE SUBMIT AN EXPANDED SANITARY RISER DIAGRAM |
| FOR REVIEW. THERE ARE AREAS WHERE IT IS EXTREMELY |
| DIFFICULT TO DETERMINE IF THE DESIGN IS CODE |
| COMPLIANT.WPB AMEND. TO FBC SEC. 107.2.1. |
| |