2019-06-28 15:11:09 | 2 ND REVIEW: JUNE 27, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18091284 |
| ADD: 2201 45TH ST. JFK NORTH ED ADDITION & RENOVATIONS |
| CONT: DPR CONSTRUCTION |
| TEL: 954-991-6200 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1) IN PROGRESS |
| -PLEASE SEND RESIDENT INSPECTOR AGREEMENT (STARTS ON |
| PAGE 9) VIA E-MAIL TO [email protected]. ALSO, INCLUDE |
| RESUMES FOR ALL INSPECTORS THAT MAY BE ON-SITE. |
| UPON APPROVAL BY CHIEF BUILDING INSPECTOR, THREE |
| ORIGINAL COPIES WILL BE REQUESTED. |
| |
| 2) SHEET 088_S001 IN THE STRUCTURAL NOTES IN THE WIND |
| DESIGN DATA THE EXPOSURE IS GIVEN AS A B EXPOSURE. IT |
| WOULD APPEAR THAT TO THE NORTHEAST AND NORTHWEST THERE |
| ARE C EXPOSURES SINCE MOST OF THESE AREAS HAVE LITTLE |
| OR NO BUILDINGS, THEY ARE GRASSLANDS, OPEN LAKES, |
| CANALS, PARKING LOTS AND HIGHWAYS. |
| 2017 FBC-B 1609.4.2 SURFACE ROUGHNESS CATEGORIES. A |
| GROUND SURFACE ROUGHNESS WITHIN EACH 45-DEGREE SECTOR |
| SHALL BE DETERMINED FOR A DISTANCE UPWIND OF THE SITE |
| AS DEFINED IN SECTION 1609.4.3 FROM THE CATEGORIES |
| DEFINED BELOW, FOR THE PURPOSE OF ASSIGNING AN EXPOSURE |
| CATEGORY AS DEFINED IN SECTION 1609.4.3. |
| SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED |
| OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30 |
| FEET. THIS CATEGORY INCLUDES FLAT OPEN COUNTRY, AND |
| GRASSLANDS. |
| -STRUCTURAL ENGINEER FEELS THAT THIS SHOULD BE EXPOSURE |
| B. |
| THIS HAS BEEN SENT TO THE BUILDING OFFICIAL FOR |
| DETERMINATION. |
| |
| 3) PENDING BUILDING OFFICIAL DETERMINATION. |
| |
| 4) OK |
| |
| 5A) PLEASE PROVIDE THE PRODUCT APPROVAL FOR STOREFRONT |
| SYSTEM BEING USED AT WINDOWS, OR INDICATE THAT IT WILL |
| BE DEFERRED. |
| |
| 5B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| PLEASE PROVIDE PRODUCT APPROVALS THAT HAVE BEEN STAMPED |
| FOR APPROVAL BY THE DESIGNER OF RECORD, OR PROVIDE |
| INDEX SHEET LISTING THE PRODUCT APPROVALS AND |
| VERIFICATION THAT WERE REVIEWED. |
| |
| 6) OK |
| |
| 7) ROOFING PRODUCT APPROVALS ? PLEASE SELECT THE SYSTEM |
| BEING USED FROM NOA 17-1221.10 AND PROVIDE INFORMATION |
| IF REQUIRED BY GENERAL LIMITATIONS. |
| IF INFORMATION IS NOT KNOWN THIS CAN BECOME A DEFERRED |
| SUBMITTAL WITH THE SUB PERMIT. |
| |
| 8) OK |
| |
| 9) OK |
| |
| 10) GEOTECHNICAL REPORT WAS NOT FOUND IN SUPPORTING |
| DOCUMENTS. PLEASE UPLOAD GEOTECHNICAL REPORT, OR TELL |
| ME WHERE IT IS LOCATED. IF IT IS COMBINED WITH ANOTHER |
| DOCUMENT PLEASE PROVIDE AS STAND ALONE DOCUMENT. |
| |
| 11) ADDITIONAL PERMIT IS BEING SUBMITTED FOR TEMP |
| WALKWAYS AND FENCING. WALKWAYS TO BE DESIGNED BY P.E. |
| AND DIGITALLY SIGNED WITH THIRD PARTY VERIFICATION. |
| 61G15-23 PE RULES FAC, FS 471 ENGINEERING FS. |
| |
| 12) OK |
| |
| 13) OK |
| |
| 14) ROOF HATCH PRODUCT APPROVAL WAS SUBMITTED |
| PREVIOUSLY. |
| IS THIS BEING USED, OR IS ACCESS PROVIDED BY EXTERIOR |
| LADDER? |
| PLEASE DELETE ROOF HATCH FROM SUPPORTING DOCUMENTS IF |
| NOT UTILIZING. |
| ACCESS LADDER TO BE ADDED TO PROVISO LIST TO PROVIDE |
| LOCATION AND ATTACHMENT. |
| |
| 15) OK |
| |
| 16A) ROOFTOP EXHAUST FANS WILL BE ADDED TO DEFERRED |
| SUBMITTAL LIST. |
| NO RESPONSE NEEDED. |
| |
| 16B)-22 OK |
| |
| 23) PLEASE SUPPLY A SURVEY FOR THIS PROPERTY INDICATING |
| THE DISTANCE FROM THE CURRENT BUILDING LOCATION TO THE |
| EAST PROPERTY LINE TO VERIFY THE EXTERIOR WALL RATING |
| FBC-B TABLE 602 AND THE AMOUNT OF ALLOWABLE OPENINGS |
| FOR UNPROTECTED AND SPRINKLERED FBC-B TABLE 705.8. |
| I COULD NOT FIND THE SURVEY IN DRAWINGS OR SUPPORTING |
| DOCUMENTS. |
| PLEASE UPLOAD THE EXISTING SURVEY. |
| |
| 24) OK |
| |
| 25) OK |
| |
| |
| |
| |
| |