2019-02-21 10:17:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) SHEET D 110 - THERE ARE NO INDICATIONS THAT THE LIFE |
| SAFETY SYSTEMS SHALL BE MAINTAINED DURING DEMO AND/OR |
| THROUGHOUT CONSTRUCTION. |
| |
| IT IS OF THE UTMOST IMPORTANCE THAT THE FIRE ALARM AND |
| FIRE SPRINKLER BE MAINTAINED AT ALL TIMES. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| |
| |
| |
| 2) SHEET A 575 - THERE ARE INDICATIONS OF CARDER |
| READERS AND ACCESS CONTROL WITHIN THE DOOR SCHEDULE. |
| |
| CARD READER AND ACCESS CONTROL SHALL BE INSTALLED UNDER |
| SPEARATE PERMIT AND SHOP DRAWINGS. |
| |
| ALL DEVICES AND EQUIPMENT FOR CARD READERS AND ACCESS |
| CONTRAL SHALL FUNCTION/OPERATE UNDER THE REQUIREMENTS |
| OF NFPA 101, CHAPTER 7, MEANS OF EGRESS. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| |
| |
| |
| 3) SHEET FP 001 - THERE ARE INDICATIONS OF FIRE |
| SPRINKLER WORK. |
| |
| ALL FIRE SPRINKLER WORK, DEMO THRU NEW CONSTRUCTION, |
| SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS |
| BY CERTIFIED FIRE SPRINKLER CONTRATORS. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| |
| |
| |
| 4) SHEET E 000 - THERE ARE NO INDICATIONS OF FIRE ALARM |
| DEVICES/ EQUIPMENT OR FIRE ALARM WORK. |
| |
| ALL FIRE ALARM WORK, DEMO THRU NEW CONSTRUCTION, SHALL |
| BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS BY |
| CERTIFIED FIRE ALARM CONTRATORS. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| |
| |
| 5) SHEET G 410 - THERE IS AN INDICATION OF A TEMPORARY |
| AMBULANCE CANOPY. THERE IS NO DETAIL PLAN SHEET OR |
| CALL-OUT DRAWING. |
| |
| IF THIS A TENT STRUCTURE, IS THE FABRIC FIRE RETARDENT, |
| SIZE, HEIGHT, SIDES, LIGHTING, ETC.? |
| |
| ANY TEMPORAY TENT STRUCTURE SHALL BE INSTALLED UNDER |
| SEPARATE PERMIT AND SHOP DRAWINGS THAT INCLUDE, THE |
| ABOVE. |
| |
| PLEASE PROVIDE DETAILS AND/OR A NOTE OF |
| ACKNOWLEDGEMENT. |
| |
| |
| |
| 6) SHEET G 410 - A CONSTRUCTION BARRIER IS INDICATED. |
| THERE IS NO DETAIL PLAN SHEET OR CALL-OUT DRAWING. |
| |
| WILL THIS AREA BE CONSTRUCTION MATERIAL, HAVE LIGHTING, |
| EXIT SIGNAGE, SIDES, SPRINKLER PROTECTION, FIRE ALARM |
| DEVICES, ETC. |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| |
| 7) SHEET G 410 - A TEMPORARY PUB ED CANOPY IS |
| INDICATED. WHAT IS THE PURPOSE AND OCCUPANCY |
| CLASSIFICATION OF THIS CANOPY? |
| |
| EDUCATION CLASSROOM, ASEEMBLY GATHERING AREA,? HOW WILL |
| IT BE CONSTRUCTED? IS IT TEMPORARY TENT WITH SIDES? |
| |
| ANY TEMPORAY TENT STRUCTURE SHALL BE INSTALLED UNDER |
| SEPARATE PERMIT AND SHOP DRAWINGS THAT INCLUDE, THE |
| ABOVE. |
| |
| PLEASE PROVIDE DETAILS AND/OR A NOTE OF |
| ACKNOWLEDGEMENT. |
| |
| |
| |
| 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 9)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |