Plan Review Notes
Plan Review Notes For Permit 18091284
Permit Number 18091284
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-02-21 10:17:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET D 110 - THERE ARE NO INDICATIONS THAT THE LIFE
 SAFETY SYSTEMS SHALL BE MAINTAINED DURING DEMO AND/OR
 THROUGHOUT CONSTRUCTION.
  
 IT IS OF THE UTMOST IMPORTANCE THAT THE FIRE ALARM AND
 FIRE SPRINKLER BE MAINTAINED AT ALL TIMES.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 2) SHEET A 575 - THERE ARE INDICATIONS OF CARDER
 READERS AND ACCESS CONTROL WITHIN THE DOOR SCHEDULE.
  
 CARD READER AND ACCESS CONTROL SHALL BE INSTALLED UNDER
 SPEARATE PERMIT AND SHOP DRAWINGS.
  
 ALL DEVICES AND EQUIPMENT FOR CARD READERS AND ACCESS
 CONTRAL SHALL FUNCTION/OPERATE UNDER THE REQUIREMENTS
 OF NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 3) SHEET FP 001 - THERE ARE INDICATIONS OF FIRE
 SPRINKLER WORK.
  
 ALL FIRE SPRINKLER WORK, DEMO THRU NEW CONSTRUCTION,
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS
 BY CERTIFIED FIRE SPRINKLER CONTRATORS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 4) SHEET E 000 - THERE ARE NO INDICATIONS OF FIRE ALARM
 DEVICES/ EQUIPMENT OR FIRE ALARM WORK.
  
 ALL FIRE ALARM WORK, DEMO THRU NEW CONSTRUCTION, SHALL
 BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS BY
 CERTIFIED FIRE ALARM CONTRATORS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
 5) SHEET G 410 - THERE IS AN INDICATION OF A TEMPORARY
 AMBULANCE CANOPY. THERE IS NO DETAIL PLAN SHEET OR
 CALL-OUT DRAWING.
  
 IF THIS A TENT STRUCTURE, IS THE FABRIC FIRE RETARDENT,
 SIZE, HEIGHT, SIDES, LIGHTING, ETC.?
  
 ANY TEMPORAY TENT STRUCTURE SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS THAT INCLUDE, THE
 ABOVE.
  
 PLEASE PROVIDE DETAILS AND/OR A NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 6) SHEET G 410 - A CONSTRUCTION BARRIER IS INDICATED.
 THERE IS NO DETAIL PLAN SHEET OR CALL-OUT DRAWING.
  
 WILL THIS AREA BE CONSTRUCTION MATERIAL, HAVE LIGHTING,
 EXIT SIGNAGE, SIDES, SPRINKLER PROTECTION, FIRE ALARM
 DEVICES, ETC.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 7) SHEET G 410 - A TEMPORARY PUB ED CANOPY IS
 INDICATED. WHAT IS THE PURPOSE AND OCCUPANCY
 CLASSIFICATION OF THIS CANOPY?
  
 EDUCATION CLASSROOM, ASEEMBLY GATHERING AREA,? HOW WILL
 IT BE CONSTRUCTED? IS IT TEMPORARY TENT WITH SIDES?
  
 ANY TEMPORAY TENT STRUCTURE SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS THAT INCLUDE, THE
 ABOVE.
  
 PLEASE PROVIDE DETAILS AND/OR A NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  