2019-02-22 15:45:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. INDICATE ON PLANS WHICH ROOMS/AREAS SHALL BE WIRED
 PER NEC 517.13.
 2. PROVIDE PANEL BOARD BONDING PER NEC 517.14.
 3. PANEL SCHEDULES SHOW DEMAND FACTORS FOR VARIOUS
 ITEMS THAT DON'T SEEM TO BE CODE COMPLIANT. FOR
 EXAMPLE, SOME LIGHTING IS SHOWN WITH A DEMAND FACTOR OF
 40%, BUT THE PLAN DOES NOT CLARIFY WHAT THESE AREAS
 ARE. THIS DEMAND FACTOR CANNOT BE APPLIED TO AREAS OF A
 HOSPITAL WHERE THE LIGHTING LOAD IS LIKELY TO BE USED
 AT ONE TIME, SUCH AS AN EMERGENCY DEPARTMENT. PROVIDE
 CLARIFICATION. ANOTHER EXAMPLE IS THE DEMAND FACTOR OF
 85% APPLIED TO SOME AREAS. WHAT IS THE CODE REFERENCE
 THAT PERMITS THIS? ALSO, THE DEMAND FACTORS FOR
 RECEPTACLE LOADS IS NOT COMPLIANT WITH NEC TABLE
 220.44. PROVIDE CORRECTIONS AS NEEDED, AND UPDATE LOAD
 SUMMARIES TO REFLECT CHANGES. NEC 220; WPB FBC 107.2.1
 4. SHEET E-701 PROVIDES LOAD SUMMARIES AND SHOWS THE
 EXISTING LOADS FOR EACH OF THOSE SUMMARIES. WHERE IS
 THIS INFORMATION FROM, HOW ARE THESE EXISTING LOADS
 DETERMINED? PROVIDE CLARIFICATION. NEC 220; WPB FBC
 107.2.1
 5. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved