2019-02-21 07:00:36 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18091284 |
| ADD: 2201 45TH ST. JFK NORTH ED ADDITION & RENOVATIONS |
| CONT: DPR CONSTRUCTION |
| TEL: 954-991-6200 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. FEB. 20/2019 |
| ACTION: DENIED |
| |
| 1) THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR ON |
| THE PROJECT AS LONG AS THERE IS STRUCTURAL STEEL BOLTED |
| OR WELDED CONNECTIONS BAR JOIST AND THE STEEL ROOF DECK |
| ANCHORING BY WELDS OR BOLTED CONNECTIONS. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 110.3.9. OTHER |
| INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| BY SECTION 109 110. HE/SHE MAY ACCEPT REPORTS OF |
| INSPECTORS OF RECOGNIZED INSPECTION SERVICES, PROVIDED |
| THAT AFTER INVESTIGATION HE/SHE IS SATISFIED AS TO |
| THEIR QUALIFICATIONS AND RELIABILITY. A CERTIFICATE |
| CALLED FOR BY ANY PROVISION OF THE TECHNICAL CODES |
| SHALL NOT BE BASED ON SUCH REPORTS UNLESS THE SAME ARE |
| IN WRITING AND CERTIFIED BY A RESPONSIBLE OFFICER OF |
| SUCH SERVICE. THE BUILDING OFFICIAL MAY REQUIRE THE |
| OWNER TO EMPLOY AN INSPECTION SERVICE IN THE FOLLOWING |
| INSTANCES: |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| FORMS ARE TO BE E-MAILED TO : [email protected] SENT AT |
| 2:09 PM 02/19/2019. |
| |
| 2) SHEET 088_S001 IN THE STRUCTURAL NOTES IN THE WIND |
| DESIGN DATA THE EXPOSURE IS GIVEN AS A B EXPOSURE. IT |
| WOULD APPEAR THAT TO THE NORTHEAST AND NORTHWEST THERE |
| ARE C EXPOSURES SINCE MOST OF THESE AREAS HAVE LITTLE |
| OR NO BUILDINGS, THEY ARE GRASSLANDS, OPEN LAKES, |
| CANALS, PARKING LOTS AND HIGHWAYS. |
| 2017 FBC-B 1609.4.2 SURFACE ROUGHNESS CATEGORIES. A |
| GROUND SURFACE ROUGHNESS WITHIN EACH 45-DEGREE SECTOR |
| SHALL BE DETERMINED FOR A DISTANCE UPWIND OF THE SITE |
| AS DEFINED IN SECTION 1609.4.3 FROM THE CATEGORIES |
| DEFINED BELOW, FOR THE PURPOSE OF ASSIGNING AN EXPOSURE |
| CATEGORY AS DEFINED IN SECTION 1609.4.3. |
| SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED |
| OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30 |
| FEET. THIS CATEGORY INCLUDES FLAT OPEN COUNTRY, AND |
| GRASSLANDS. |
| |
| 3) SINCE THE EXPOSURE WOULD BE A C EXPOSURE FOR 179 |
| VASD THE PRESSURES WILL INCREASE FOR THE MULTIPLIER FOR |
| THE HEIGHT OF THE BUILDING FOR THE EXPOSURE C. SEE |
| TABLE 1609.7(2). |
| |
| 4) PLEASE ALSO NOTE ON SHEET 088_S001 UNDER THE HEADING |
| 2.4.1 EXTERIOR COMPONENTS & CLADDING |
| THE COLUMN OF PRESSURES FOR CORNERS WALL ZONE 5 THE |
| NEGATIVE PRESSURES FOR 20 SQ. FT. AND 100 SQ. FT. ARE |
| THE SAME AND THE PRESSURES FOR 50 SQ. FT. ARE HIGHER |
| THAN FOR THE 20 SQ. FT. IT WOULD APPEAR THIS IS A TYPO, |
| PLEASE PROVIDE ADDITIONAL INFORMATION, PLEASE. |
| 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 5A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| CONCRETE INSULATION, ROOF TOP VENTILATORS & CURBS |
| |
| 5B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 7) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| CALCULATION PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| |
| 8) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL |
| FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE |
| MANUFACTURERS INSTALLATION BROCHURE PROVIDING |
| COMPLIANCE WITH 2014 FBC-B SECTIONS; |
| 1408.2 PERFORMANCE CHARACTERISTICS. |
| 1408.2 PERFORMANCE CHARACTERISTICS. |
| 1408.3 STRUCTURAL DESIGN. |
| 1408.4 WEATHER RESISTANCE. |
| 1408.4.1 EIFS WITH DRAINAGE. |
| 408.4.1.1 WATER-RESISTIVE BARRIER. |
| 1408.5 INSTALLATION |
| |
| 9) IF EITHER THE CONTRACTOR OR DESIGN PROFESSIONAL |
| WOULD LIKE TO SUBMIT THE PRODUCT APPROVALS AFTER PERMIT |
| ISSUANCE PLEASE NOTE SO ON THE PLANS AS A DEFERRED |
| SUBMITTAL. |
| |
| 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 10) SHEET 088_S001 UNDER THE HEADING OF FOUNDATION AND |
| THE GEOTECHNICAL REPORT IT DOES NOT INDICATE A REPORT |
| NUMBER NOR UNDER THE SOIL BEARING CAPACITY FOR ISOLATED |
| FOOTING OR CONTINUOUS FOOTING THE PSF IS LEFT BLANK. |
| PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION: |
| |
| 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, |
| STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR |
| WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED |
| IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| BE CONDUCTED. |
| |
| 11) SHEET 018G410 THE 1ST FLOOR PHASING PLAN WHICH |
| INCLUDES A TEMPORARY AMBULANCE CANOPY, TEMPORARY |
| ENCLOSED WALKWAY AND A 2ND TEMPORARY CANOPY FOR PUBLIC |
| ED. AND A 2ND ENCLOSED WALKWAY WITH LIGHTS AND |
| SPRINKLERS. ADDITIONAL INFORMATION IS REQUIRED? |
| 107.2.1.2. |
| |
| 11A) THE PLAN INDICATES THAT THE TEMPORARY WALKWAY HAS |
| LIGHTS AND FIRE SPRINKLERS BUT NOT THE TEMP. AMBULANCE |
| CANOPY, OR PUBLIC EDUCATION CANOPIES DO THEY HAVE |
| LIGHTS AND FIRE SPRINKLERS AS WELL? |
| 2017 FBC-B 3103.1.1 CONFORMANCE. TEMPORARY STRUCTURES |
| AND USES SHALL CONFORM TO THE STRUCTURAL STRENGTH, FIRE |
| SAFETY, AND MEANS OF EGRESS, ACCESSIBILITY, LIGHT, |
| VENTILATION AND SANITARY REQUIREMENTS OF THIS CODE AS |
| NECESSARY TO ENSURE PUBLIC HEALTH, SAFETY AND GENERAL |
| WELFARE. |
| |
| 11B) IS THE TEMPORARY WALKWAYS AND AMBULANCE & PUBLIC |
| EDUCATION CANOPIES GOING TO BE PART OF THIS PERMIT OR |
| COME IN UNDER A SEPARATE TENT PERMIT. 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 11C) HOW LONG IS THE WALKWAYS, AMBULANCE CANOPY & |
| PUBLIC EDUCATION CANOPIES GOING TO BE ERECTED? |
| THE BUILDING CODE 2017 FBC-B SECTION: |
| 3103.1 THE PROVISIONS OF SECTIONS 3103.1 THROUGH 3103.4 |
| SHALL APPLY TO STRUCTURES ERECTED FOR A PERIOD OF LESS |
| THAN 180 DAYS. TENTS AND OTHER MEMBRANE STRUCTURES |
| ERECTED FOR A PERIOD OF LESS THAN 180 DAYS SHALL COMPLY |
| WITH THE FLORIDA FIRE PREVENTION CODE. THOSE ERECTED |
| FOR A LONGER PERIOD OF TIME SHALL COMPLY WITH |
| APPLICABLE SECTIONS OF THIS CODE. |
| |
| THE AMBULANCE AND WALKWAY CANOPIES WILL NEED TO SHOW |
| ENGINEERING FOR THE WIND SPEED REQUIRED FOR 180 VULT, |
| OR WILL THE STRUCTURES BE REMOVED IN CASE OF |
| HURRICANES, WHAT THEN WOULD HAPPEN TO THE FIRE |
| SPRINKLER PIPING WITHIN THE STRUCTURES? |
| |
| 11D) WITH THE EXTENSION OF THE EXIT SHOWN IN THE PLAN, |
| IT IS NOT CLEAR IF THE ENCLOSED WALKWAY FOR THE |
| AMBULANCE CANOPY ONLY HAS THE ONE EXIT AT THE END OF |
| THE ENCLOSURE OR IF AT THE MAIN BUILDING EXIT THERE IS |
| A SIDE OPENING TO ALLOW THE EXITING OF THE ENCLOSURE |
| DIRECTLY FROM THE BUILDING? |
| 2017 FBC-B 3103.4 MEANS OF EGRESS. TEMPORARY STRUCTURES |
| SHALL CONFORM TO THE MEANS OF EGRESS REQUIREMENTS OF |
| CHAPTER 10 AND SHALL HAVE AN EXIT ACCESS TRAVEL |
| DISTANCE OF 100 FEET (30 480 MM) OR LESS. |
| |
| 11E) IN THE TENT FOR THE AMBULANCES ARE THEIR GOING TO |
| HAVE SIDES ENCLOSING THE TENT AS THE WALKWAY, HOW WILL |
| THE VENTILATION REQUIREMENTS BE MET AND CARBON MONOXIDE |
| FROM THE AMBULANCES BE REMOVED FROM THE TENT. |
| 2017 FBC-B 3103.1.1 CONFORMANCE. TEMPORARY STRUCTURES |
| AND USES SHALL CONFORM TO THE STRUCTURAL STRENGTH, FIRE |
| SAFETY, AND MEANS OF EGRESS, ACCESSIBILITY, LIGHT, |
| VENTILATION AND SANITARY REQUIREMENTS OF THIS CODE AS |
| NECESSARY TO ENSURE PUBLIC HEALTH, SAFETY AND GENERAL |
| WELFARE. |
| |
| 12) SHEET 019G411 UNDER THE HEADING PHASING NOTE S NOTE |
| # 6 STATES THAT DURING CONSTRUCTION AT NO TIME SHALL |
| TEMPORARY CONSTRUCTION BARRIERS LIMIT THE CORRIDOR |
| WIDTH TO LESS THAN 6 FEET. THERE IS NOTE ON THE PLANS |
| FOR A TEMPORARY CORRIDOR TO BE 5 FEET 11 57/64 INCHES |
| IN WIDTH. WHICH NOTE TAKES PRECEDENCE? THE NOTE IS |
| LOCATED IN A CORRIDOR BETWEEN THE CLEAN SUPPLY ROOM AND |
| PATIENT TOILET. 107.2.1.2 ADDITIONAL INFORMATION |
| REQUIRED. |
| |
| 13) SHEET 053_A250 DETAIL # 10 SHOWS A 1 HOUR |
| HORIZONTAL SHAFT THAT IS HANGING FROM THE CEILING. THIS |
| SAME DETAIL INDICATES SEE SHEET G150 DETAIL 7Z FOR THE |
| 1 HOUR SHAFT ENCLOSURE/ UL# U415. THE UL LISTING U 415 |
| DOES SHOW THE USE OF SHAFTWALL SYSTEM FOR NONBEARING |
| WALL SYSTEMS. NOWHERE IN THE UL 415 STANDARD DOES IT |
| STATE THAT THIS SHAFT WALL IS TO BE HUNG FROM THE |
| CEILING. THE SHAFTWALL SYSTEM SHOWS THAT IT WAS ONLY |
| TESTED FOR VERTICAL USE, (A WALL SYSTEM), IT DOES NOT |
| INDICATE THAT THE SYSTEM WAS EVER TESTED FOR THE WALL |
| ASSEMBLY TO BE TURNED ON ITS SIDE AND BE USED |
| HORIZONTALLY. WE WILL NEED TO SEE ACTUAL TEST DATA FROM |
| UL WHERE THIS ASSEMBLY WAS TESTED HANGING FROM THE |
| CEILING, AND TESTED FROM BOTH SIDES SINCE THIS IS |
| SHAFTWALL CONSTRUCTION WITH DIFFERENT COMPONENTS MAKING |
| UP THE WALL SYSTEM. |
| |
| 2017 FBC-B 707.5 CONTINUITY. FIRE BARRIERS SHALL EXTEND |
| FROM THE TOP OF THE FOUNDATION OR FLOOR/CEILING |
| ASSEMBLY BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF |
| SHEATHING, SLAB OR DECK ABOVE AND SHALL BE SECURELY |
| ATTACHED THERETO. SUCH FIRE BARRIERS SHALL BE |
| CONTINUOUS THROUGH CONCEALED SPACE, SUCH AS THE SPACE |
| ABOVE A SUSPENDED CEILING. JOINTS AND VOIDS AT |
| INTERSECTIONS SHALL COMPLY WITH SECTIONS 707.8 AND |
| 707.9. |
| |
| 14) THE SHEET 054_A300 AND 117_M301 BOTH SHOW A |
| MECHANICAL PENTHOUSE. PLEASE INDICATE HOW ONE GETS UP |
| TO THE PENTHOUSE TO WORK ON THE MECHANICAL EQUIPMENT. |
| PLEASE SHOW COMPLIANCE WITH THE 2017 |
| FBC-B SECTIONS: |
| 1011.12 STAIRWAY TO ROOF. EXCEPTION: OTHER THAN WHERE |
| REQUIRED BY SECTION 1011.12.1, IN BUILDINGS WITHOUT AN |
| OCCUPIED ROOF ACCESS TO THE ROOF FROM THE TOP STORY |
| SHALL BE PERMITTED TO BE BY AN ALTERNATING TREAD |
| DEVICE, A SHIPS LADDER OR A PERMANENT LADDER. |
| |
| 1011.12.2 ROOF ACCESS. WHERE A STAIRWAY IS PROVIDED TO |
| A ROOF, ACCESS TO THE ROOF SHALL BE PROVIDED THROUGH A |
| PENTHOUSE COMPLYING WITH SECTION 1510.2. |
| EXCEPTION: IN BUILDINGS WITHOUT AN OCCUPIED ROOF, |
| ACCESS TO THE ROOF SHALL BE PERMITTED TO BE A ROOF |
| HATCH OR TRAP DOOR NOT LESS THAN 16 SQUARE FEET IN AREA |
| AND HAVING A MINIMUM DIMENSION OF 2 FEET. |
| |
| 1011.16 LADDERS. PERMANENT LADDERS SHALL NOT SERVE AS A |
| PART OF THE MEANS OF EGRESS FROM OCCUPIED SPACES WITHIN |
| A BUILDING. PERMANENT LADDERS SHALL BE PERMITTED TO |
| PROVIDE ACCESS TO THE FOLLOWING AREAS: |
| 1.SPACES FREQUENTED ONLY BY PERSONNEL FOR MAINTENANCE, |
| REPAIR OR MONITORING OF EQUIPMENT. |
| 5.NONOCCUPIED ROOFS THAT ARE NOT REQUIRED TO HAVE |
| STAIRWAY ACCESS IN ACCORDANCE WITH SECTION |
| 1011.12.1. |
| 6.LADDERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH |
| SECTION 306.5 OF THE FLORIDA BUILDING CODE, |
| MECHANICAL. |
| |
| 15) SHEET 054_A300 ROOF PLAN NOTE 10. STATES THAT ROOF |
| PAVERS OR BUILT UP WALKWAYS TO BE PROVIDED AND |
| INSTALLED AS NEEDED TO ACCESS MECHANICAL EQUIPMENT FROM |
| ROOF HATCHES. PLEASE SPECIFY EITHER ROOF PAVERS OR |
| BUILT UP WALKWAYS. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| W.P.B. ADMINISTRATIVE CODE 2017. DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| AS A SUBSTITUTE FOR SPECIFIC INFORMATION". |
| |
| 16A) THE ROOFTOP PLAN 054_A300 INDICATES NEW ROOF TOP |
| EXHAUST FANS, THE MECHANICAL SHEET 121_M404 DETAIL 1 |
| &10 BOTH INDICATE EXHAUST FANS AND OR CURBS. NOTE 7 IN |
| DETAIL 1 INDICATE FAN TO HAVE A NOA, PRODUCT APPROVAL. |
| IN DETAIL 10 INDICATE AN ENGINEER IS TO PROVIDE THE |
| ATTACHMENT METHOD OF THE FAN TO THE ROOF CURB AND CURB |
| TO THE ROOF FRAMING. SHEET 101_S402 SHOW THE ROOF TOP |
| REINFORCEMENT OF ROOF FRAMING AT THE ROOF DECK OPENING |
| BUT NOT THE CURB TO THE ROOF FRAMING. |
| |
| LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP |
| EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, |
| PIPE SUPPORTS ON THE ROOF DETAILED ATTACHMENT TO THE |
| ROOF FRAMING & DECK AS WELL AS FROM THE CURB OR ROOF |
| STAND TO THE EQUIPMENT ABOVE. |
| |
| 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| |
| 16B) SHEET 121_M404 DETAIL 11 SHOWS A ROOF TOP PIPE |
| SUPPORT. THE NOTE ON THE PLANS INDICATES THE TIE DOWN |
| DETAILS ARE BY THE STRUCTURAL ENGINEER REGISTERED IN |
| THE STATE OF FLORIDA BASED ON THE AREA WIND LOADING |
| REQUIREMENTS, PLEASE SHOW CODE COMPLIANCE. LATERAL |
| FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP EQUIPMENT, |
| CURBS, FANS OR A/C STANDS, AND OR VENTS, PIPE SUPPORTS |
| ON THE ROOF DETAILED ATTACHMENT TO THE ROOF FRAMING & |
| DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE |
| EQUIPMENT ABOVE. |
| |
| 17) SHEET 063_A501 DETAILS 1 & 3 BOTH SHOW THE USE OF 2 |
| INCH EFIS ON 5/8 INCH EXTERIOR GRADE PLYWOOD. |
| PLEASE NOTE THE CONSTRUCTION TYPE FOR THIS BUILDING IS |
| I-B. PLEASE REVIEW THE 2017 FBC-B SECTIONS: |
| |
| 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE MATERIALS SHALL |
| BE PERMITTED IN BUILDINGS OF TYPE I OR II CONSTRUCTION |
| IN THE FOLLOWING APPLICATIONS AND IN ACCORDANCE WITH |
| SECTIONS 603.1.1 THROUGH 603.1.3: |
| 1.FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| 1.1.NONBEARING PARTITIONS WHERE THE REQUIRED |
| FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
| 1.2.NONBEARING EXTERIOR WALLS WHERE |
| FIRE-RESISTANCE-RATED CONSTRUCTION IS NOT REQUIRED. |
| 1.3.ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES, |
| FRAMING AND DECKING. |
| |
| 18) SHEET 063_A501 DETAILS 3 & 4 BOTH SHOW THE USE OF |
| FIREPROOFING OF THE STEEL FRAMING ALSO SHEET 064_A525 |
| DETAILS 1,2 & 5. PLEASE PROVIDE CODE COMPLIANCE OF FIRE |
| RESISTANCE RATING REQUIREMENT FOR BUILDINGS ELEMENTS |
| SEE TABLE 601 AND FOOTNOTES OF THE 2017 FBC-B. THE |
| ARCHITECTURAL SHEET ALSO STATES STEEL BEAM WITH SPRAY |
| APPLIED FIREPROOFING, COORDINATE WITH STRUCTURAL STEEL |
| DRAWINGS. SHEET 010_G164 |
| DOES HAVE FIRE RESISTANCE RATINGS FOR BAR JOIST BUT |
| WITHIN THE SYSTEM THERE ARE DIFFERENT OR ALTERNATE |
| METHODS OF APPLICATION, NO ONE METHOD HAS BEEN |
| IDENTIFIED FOR USE IN THIS BUILDING. THERE IS NO |
| INFORMATION ABOUT FIRE RESISTANCE RATING FOR THE STEEL |
| COLUMNS. |
| |
| 19) SHEET 069_A577 THERE ARE 3 DETAILS DETAIL # 1 & 2 |
| DOES NOT INDICATE THE TYPE OF SHEATHING TO BE |
| INSTALLED. BOTH DETAIL 2 & 3 BOTH INDICATE SEE DETAIL # |
| 4 SHEET 011_G165. 2 INCH EFIS ON 5/8 INCH EXTERIOR |
| SHEATHING. PLEASE NOTE THE CONSTRUCTION TYPE FOR THIS |
| BUILDING IS I-B. PLEASE REVIEW THE 2017 FBC-B SECTIONS: |
| |
| 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE MATERIALS SHALL |
| BE PERMITTED IN BUILDINGS OF TYPE I OR II CONSTRUCTION |
| IN THE FOLLOWING APPLICATIONS AND IN ACCORDANCE WITH |
| SECTIONS 603.1.1 THROUGH 603.1.3: |
| 1.FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| 1.1.NONBEARING PARTITIONS WHERE THE REQUIRED |
| FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
| 1.2.NONBEARING EXTERIOR WALLS WHERE |
| FIRE-RESISTANCE-RATED CONSTRUCTION IS NOT REQUIRED. |
| 1.3.ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES, |
| FRAMING AND DECKING. |
| |
| 20) SHEET 076_A800 PLEASE REVIEW THE UPPER LEFT HAND |
| BREAK ROOM CABINETS, DETAIL NOT GIVEN A DETAIL NUMBER. |
| THE SHELF THAT THE MICROWAVE SITS ON IS 4 FOOT 8 INCHES |
| ABOVE FINISH FLOOR, OUT OF REACH RANGES. |
| SEE THE 2017 FBC-ACCESSIBILITY CODE SECTIONS: |
| |
| 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1 |
| UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. |
| 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| OBSTRUCTED HIGH REACH. |
| |
| 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL |
| BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| SPECIFIED IN 308.309.4 OPERATION. OPERABLE PARTS SHALL |
| BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| (22.2 N) MAXIMUM. |
| |
| 21A) SHEET 076_A800 PLEASE REVIEW DETAIL 11. THIS |
| DETAIL GIVES AN ALTERNATE POSITION FOR A MICROWAVE. IT |
| IS SHOWN ON AN UPPER CABINET SHELF AT A HEIGHT OF IS 4 |
| FOOT 8 INCHES ABOVE FINISH FLOOR, OUT OF REACH RANGES. |
| SEE THE 2017 FBC-ACCESSIBILITY CODE SECTIONS: |
| |
| 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1 |
| UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. |
| 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| OBSTRUCTED HIGH REACH. |
| |
| 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL |
| BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| SPECIFIED IN 308.309.4 OPERATION. OPERABLE PARTS SHALL |
| BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| (22.2 N) MAXIMUM. |
| |
| 21B) IN THE SAME DETAIL AN ALTERNATE POSITION IS SHOWN |
| ON THE COUNTERTOP. THIS POSITION IS CODE COMPLIANT BUT |
| SHOWN AS AN ALTERNATE POSITION, THE LOCATION HAS TO BE |
| SPECIFIC. 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.2.1. |
| W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| THE TECHNICAL CODES HALL NOT BE CITED AS A WHOLE OR IN |
| PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS |
| A SUBSTITUTE FOR SPECIFIC INFORMATION. CONSTRUCTION |
| DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 22) SHEET 007_A801 PLEASE REVIEW DETAIL 5 THE STAFF |
| LOUNGE AND DETAIL 8 THE EMS LOUNGE. THESE DETAIL GIVES |
| AN ALTERNATE POSITION FOR A MICROWAVE. IT IS SHOWN ON |
| AN UPPER CABINET SHELF AT A HEIGHT OF IS 4 FOOT 8 |
| INCHES ABOVE FINISH FLOOR, OUT OF REACH RANGES. |
| SEE THE 2017 FBC-ACCESSIBILITY CODE SECTIONS: |
| |
| 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1 |
| UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. |
| 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| OBSTRUCTED HIGH REACH. |
| |
| 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL |
| BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| SPECIFIED IN 308.309.4 OPERATION. OPERABLE PARTS SHALL |
| BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| (22.2 N) MAXIMUM. |
| |
| 23) PLEASE SUPPLY A SURVEY FOR THIS PROPERTY INDICATING |
| THE DISTANCE FROM THE CURRENT BUILDING LOCATION TO THE |
| EAST PROPERTY LINE TO VERIFY THE EXTERIOR WALL RATING |
| FBC-B TABLE 602 AND THE AMOUNT OF ALLOWABLE OPENINGS |
| FOR UNPROTECTED AND SPRINKLERED FBC-B TABLE 705.8. |
| |
| 24) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE |
| REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA |
| PROJECT DOX UPON NOTIFICATION BY THIS OFFICE. |
| NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL |
| FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT |
| (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT |
| FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE |
| FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN |
| BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT |
| ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| YOUR PROJECT OR EMAIL IT TO: [email protected] |
| PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 |
| N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL. |
| |
| 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |