Plan Review Notes For Permit 18091252 |
Permit Number |
18091252 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-31 09:53:19 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA | | CODES/STANDARDS | | | | | | THE INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS OF: | | | | NFPA? 37, STANDARD FOR THE INSTALLATION AND USE OF | | STATIONARY COMBUSTION ENGINES AND GAS TURBINES, 2015 | | EDITION | | | | NFPA? 110, STANDARD FOR EMERGENCY AND STANDBY POWER | | SYSTEMS, 2013 EDITION | | | | NFPA 70?, NATIONAL ELECTRICAL CODE?, 2014 EDITION | | | | PLEASE REVIEW TO ENSURE COMPLIANCE AND PROVIDE AN | | APPLICABLE NOTE. | | | | | | | | 2) THERE ARE NO INDICATIONS FOR THE LOCATIONOF EXHAUST | | OUTLETS AND/OR PIPING. | | | | 8.2.3 EXHAUST SYSTEM TERMINATION. | | 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE | | STRUCTURE | | AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF | | COMBUSTION | | WILL DISCHARGE TO A SAFE LOCATION. | | 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE | | DIRECTED TOWARD | | COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES | | CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR | | COMBUSTIBLE | | DUSTS. | | | | PLEASE PROVIDE SPECIFIC DETAILS OF THE EXHAUST AND | | INCLUDE WINDOW AND DOOR LOCATIONS. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|