Plan Review Notes
Plan Review Notes For Permit 18091252
Permit Number 18091252
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-10-31 09:53:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA
 CODES/STANDARDS
  
  
 THE INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS OF:
  
 NFPA? 37, STANDARD FOR THE INSTALLATION AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, 2015
 EDITION
  
 NFPA? 110, STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS, 2013 EDITION
  
 NFPA 70?, NATIONAL ELECTRICAL CODE?, 2014 EDITION
  
 PLEASE REVIEW TO ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE.
  
  
  
 2) THERE ARE NO INDICATIONS FOR THE LOCATIONOF EXHAUST
 OUTLETS AND/OR PIPING.
  
 8.2.3 EXHAUST SYSTEM TERMINATION.
 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE
 STRUCTURE
 AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF
 COMBUSTION
 WILL DISCHARGE TO A SAFE LOCATION.
 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE
 DIRECTED TOWARD
 COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES
 CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR
 COMBUSTIBLE
 DUSTS.
  
 PLEASE PROVIDE SPECIFIC DETAILS OF THE EXHAUST AND
 INCLUDE WINDOW AND DOOR LOCATIONS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL