Plan Review Notes
Plan Review Notes For Permit 18091158
Permit Number 18091158
Review Stop B
Sequence Number 1
Notes
Date Text
2018-10-06 13:08:30****CORRECTIONS****
 REVISED 10/11
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. DELEGATED ENGINEERING IS TO BE REVIEWED BY
 STRUCTURAL ENGINEER OF RECORD, FAC61G15-23.
  
 2. PRECAST CALCS SHOW A DESIGN OF 170MPH, SEE COMMENT
 #4 AND CORRELATE IF NECESSARY.
  
 3. PRECAST SHORING IS NOT DIGITALLY SIGNED. AS THE
 ENGINEER HAS A DIGITAL SIGNATURE, PLEASE SEND THE
 ORIGINAL TO ME VIA EMAIL (NO MARKUPS AFTER SIGNING AS
 THAT WILL INVALIDATE THE SEAL).
  
 4. GS001, WIND DESIGN CRITERIA IS IMPORTANCE FACTOR
 III, 170MPH; SHOULDN'T THIS BE 180MPH? SEE FBC B 1609,
 ALSO THE FOLLOWING WEBSITE:
  
 HTTP://WINDSPEED.ATCOUNCIL.ORG/
  
 170MPH IS OK FOR IMPORTANCE FACTOR II. EITHER REVISE
 WIND SPEED OR IMPORTANCE FACTOR TO CORRELATE, MAKE SURE
 THAT PRECAST MATCHES.
  
 5. NA
  
 6. FS553, PROVIDE PRIVATE PROVIDER STAMP AND AFFIDAVIT.
  
  
  
  
  
  
  