Review Stop E
Sequence Number 1
Notes
Date Text
2018-10-09 15:37:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E-6.00, METER CENTER MC 1A1 IS SHOWN WITH A
 1200 AMP MAIN LUG ONLY CONFIGURATION. A MAIN BREAKER IS
 REQUIRED. MAINS SHOULD BE LABLELED. PROVIDE CORRECTION.
 NEC 230.2(E), 230.70, 230.71, 230.72
 2. SHEET E-6.02, METER CENTER MC 1B1 IS SHOWN WITH A
 1000 AMP MAIN LUG ONLY CONFIGURATION. A MAIN BREAKER IS
 REQUIRED. MAINS SHOULD BE LABLELED. PROVIDE CORRECTION.
 NEC 230.2(E), 230.70, 230.71, 230.72
 3. PROVIDE ARC ENERGY REDUCTION FOR THE BREAKERS IN
 COMMENT 1 AND 2. NEC 240.87
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  