2018-11-07 16:00:42 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 1. A1.00, FBC 107, I WAS UNABLE TO LOCATE THE NEW |
| FLAGPOLE OR ASSOCIATED FLAGPOLE ENGINEERING AND DETAIL. |
| EITHER REMOVE THE REFERENCE FROM THE NARRATIVE AND |
| CONFIRM THAT THIS IS NOT INSTALLED, OR REVISE SITE PLAN |
| AND REVISION DESCRIPTION TO INCLUDE. UPON REQUEST THE |
| FLAGPOLE CAN BE ADDED TO THE SCOPE OF ONE OF THE |
| PERMITS (SHOULD BE THE BUILDING IT IS CLOSEST TO), |
| ENGINEERING TO BE SUBMITTED AS A SUBMITTAL. THIS IS |
| TYPICALLY REQUIRED TO BE A SEPARATE PERMIT BUT I HAVE |
| NO OBJECTION TO THIS BEING INCLUDED IN THE SCOPE OF THE |
| BUILDING PERMIT IF ZONING HAS NO OBJECTION. |
| |
| 2. A1.03, FBC B 1009.7.4, STAIR RISER IS TO BE 7? MAX |
| UNLESS ONE OF THE EXCEPTIONS IS APPLICABLE. REVISE PLAN |
| TO INCLUDE EXCEPTION. THE NOTE STATES THAT THIS |
| CONDITION OCCURS AT BUILDINGS III & IV. AS THESE |
| BUILDINGS ARE 6 UNITS (16070880, 16071058) R2, |
| EXCEPTION 5 DOES NOT APPEAR APPLICABLE AS THE STAIR IS |
| LOCATED OUTSIDE; IS THIS CORRECT? SEE ALSO FBC A 504.2 |
| IF THIS PROJECT IS SUBJECT TO ACCESSIBILITY. IT APPEARS |
| THAT THE STAIRS DO NOT SERVE ACCESSIBLE UNITS; PLEASE |
| CONFIRM. |
| |
| 3. THERE ARE A NUMBER OF REFERENCES TO THE ?ADA |
| CONSULTANT? IN THE NARRATIVE. PLEASE ADVISE; IS THIS |
| PROJECT SUBJECT TO ADA/ FBC 2014 ACCESSIBIITY DUE TO |
| FEDERAL FUNDS RATHER THAN GOVERNED BY FBC 2014 |
| ACCESSIBILITY, FAIR HOUSING? IF NOT, PLEASE STATE THIS |
| IN THE RESPONSE LETTER. NOTE THAT SOME UNITS ARE SHOWN |
| AS FULLY ADA COMPLIANT. |
| |
| SEE FBC A 233.2 RESIDENTIAL DWELLING UNITS PROVIDED BY |
| ENTITIES SUBJECT TO HUD SECTION 504 REGULATIONS. |
| WHERE FACILITIES WITH RESIDENTIAL DWELLING UNITS ARE |
| PROVIDED BY ENTITIES SUBJECT TO REGULATIONS ISSUED BY |
| THE DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT (HUD) |
| UNDER SECTION 504 OF THE REHABILITATION ACT OF 1973, AS |
| AMENDED, SUCH ENTITIES SHALL PROVIDE RESIDENTIAL |
| DWELLING UNITS WITH MOBILITY FEATURES COMPLYING WITH |
| 809.2 THROUGH 809.4 IN A NUMBER REQUIRED BY THE |
| APPLICABLE HUD REGULATIONS. RESIDENTIAL DWELLING UNITS |
| REQUIRED TO PROVIDE MOBILITY FEATURES COMPLYING WITH |
| 809.2 THROUGH 809.4 SHALL BE ON AN ACCESSIBLE ROUTE AS |
| REQUIRED BY 206. IN ADDITION, SUCH ENTITIES SHALL |
| PROVIDE RESIDENTIAL DWELLING UNITS WITH COMMUNICATION |
| FEATURES COMPLYING WITH 809.5 IN A NUMBER REQUIRED BY |
| THE APPLICABLE HUD REGULATIONS. ENTITIES SUBJECT TO |
| 233.2 SHALL NOT BE REQUIRED TO COMPLY WITH 233.3. |
| |
| 4. A2.05, FBC 107, SCOPE AND NATURE OF WALL CHANGES ARE |
| NOT CLEAR. THERE IS A SECTION MARKER C A4.01; IT |
| APPEARS THAT REVISING THIS MAY CLARIFY WALL CHANGE, OR |
| ADD NOTES ON THE PLAN. GRAPHICS AT THE WALL CHANGED BUT |
| I WAS UNABLE TO LOCATE LANGUAGE THAT DESCRIBED THE |
| CHANGE. NO WALL TAGS WERE REVISED. |
| |
| 5. A4.03, A4.04, FBC 107, NARRATIVE STATES ?UPDATE NOT |
| TO COMPLY WITH P-531 REQUIREMENTS?; PLEASE CLARIFY. IS |
| P531 A REQUIRED FIRE RATED ASSEMBLY? SHOULD NARRATIVE |
| STATE THAT THE UPDATE IS TO COMPLY? |
| |
| 6. A5.04, 5.08, 5.09, 5.10, CLARIFY CHANGES, NOT IN |
| NARRATIVE. FOR EXAMPLE, SEE A5.10. A DELTA 19 |
| COORDINATION IS NOTED BUT NOTHING CLOUDED AS REVISION |
| 19. |
| |
| 7. A6.04 NARRATIVE STATES CHANGES ARE ADA RELATED, |
| UNABLE TO LOCATE THE CHANGES (CHANGE APPEARS TO BE |
| EXHAUST DUCT COORDINATION). EITHER REVISE PLAN TO |
| INCLUDE CLOUDS SHOWING ADA CHANAGES OR REVISE |
| NARRATIVE. |
| |
| |
| |