2018-10-18 16:07:20PLUMBING COMMENTS: APPROVED
  
 PROVISO
 1. TUB/SHOWER CONTROL VALVE(S) SHALL BE PRESSURE
 BALANCED PB, THERMOSTATIC MIXING (TM) OR COMBINATION
 PB/TM VALVE TYPES WITH HIGH TEMPERATURE LIMITING STOP.
 FBC RES P2708.4
 2. PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLIES TO
 ICE LINE, DISHWASHER AND CLOTHES WASHER. FBC RES
 P2903.5
 3. THE VALVES FOR THE STACKABLE WASHING MACHINE(S)
 SHALL BE ACCESSIBLE. FBC RES P2903.9.3
 4. P3105.1 DISTANCE OF TRAP FROM VENT EXCEPT FOR WATER
 CLOSETS SHALL COMPLY WITH THE REQUIREMENTS SET FORTH IN
 TABLE P3105.1.
 5. HAND HELD SHOWER IF FURNISHED, REQUIRES AN
 ATMOSPHERIC VACUUM BREAKER AT SHOWER ARM OUTLET. FBC
 RES P2708.5
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER