2018-10-07 16:48:49 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 |
| 2. NOTE 2 FOR AFCI PROTECTION SHOWN IN NOT CODE |
| COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| 3. NOTE 4 STATES THAT RECEPTACLES SHALL BE TAMPER |
| RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| CORRECTION. NEC 406.12; FBC RE E4002.14 |
| 4. RISER DIAGRAM SHOWS A FEED FROM THE METER TO THE |
| INTERIOR PANEL WHICH IS LOCATED IN THE LAUNDRY ROOM. |
| CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR |
| DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE |
| IN THIS FASHION. PROVIDE EITHER A MAIN ON THE OUTSIDE |
| OF THE HOME, OR INSTALL THE CONDUCTORS UNDER THE SLAB. |
| IF CONDUCTORS ARE INSTALLED UNDER THE SLAB, THEN THERE |
| SHOULD NOT BE AN EQUIPMENT GROUNDING CONDUCTOR IN THIS |
| CONDUIT. PROVIDE CORRECTIONS. NEC 230.70, 250.6; FBC RE |
| E3601.6 |
| 5. IT APPEARS THAT PANEL A IS FED FROM THE METER |
| LOCATED ON A SEPARATE STRUCTURE (GUEST HOUSE). PROVIDE |
| GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A BUILDING |
| OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH CIRCUIT. |
| NEC 250.32; FBC RE3607.3 |
| 6. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL |
| HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| 210.8(A)(9); FBC RE E3902.9 |
| 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 8. PROVIDE ACCURATE LOAD CALCULATION BASED ON FORMAT |
| SPECIFIED IN THE FLORIDA BUILDING CODE RESIDENTIAL. FBC |
| RE E3602.2 |
| 9. CIRCUIT 21 SHOWS THE DINING ROOM RECEPTACLE CIRCUIT |
| ON 14 GAUGE WIRE AND A 15 AMP BREAKER. PROVIDE |
| CORRECTION. NEC 210.52(B)(2); FBC RE E3703.2 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |