2018-10-10 14:15:01 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18091124 |
| REVIEWED: OCTOBER 10, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| |
| 1. [FBC 107.2.5]PROVIDE FLOOR LAYOUT PLAN TO SHOW SQ. |
| FOOTAGE, MATERIAL TYPE AND PROJECT DATA. DATA TO |
| INCLUDE TYPE OF CONSTRUCTION, SPRINKLERED Y/N, CEILING |
| SYSTEM(DEPTH AND ALL MATERIALS) AND FINISH |
| CLASSIFICATION A, B OR C. |
| NOTE: PLEASE MAKE SURE THE REPORTS MATCH YOUR CEILING |
| ASSEMBLY |
| |
| 2. IS ALL OF THE FLOORING TILE AND WHY TWO DIFFERENT |
| UNDERLAYMENTS? |
| |
| 3. I RECEIVED ONE COPY OF RCU-250 REPORT, BUT PLEASE |
| PRINT TWO COPIES THAT ARE MORE LEGIBLE THAN THE ONE |
| PROVIDED. |
| |
| 4. PROVIDE ONE ADDITIONAL COPY OF REPORT FOR PROFLEX |
| MSC-90. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |