Plan Review Notes
Plan Review Notes For Permit 18091065
Permit Number 18091065
Review Stop P
Sequence Number 1
Notes
Date Text
2018-11-15 10:53:411) THE PLUMBING PLANS SHALL BEAR THE SEAL AND SIGNATURE
 OF THE DESIGN PROFESSIONAL OF RECORD PER FL. ADMIN.
 CODE RULE 61G15-23.001.
 2) THE LEVEL OF ALTERATION SHALL BE LISTED ON THE PLANS
 PER THE 2017 FBC-EXISTING BUILDING CODE SEC.301.1.
 3) SHT. LS 1.1 - THE EDITION OF CODES IN EFFECT FOR
 THIS PROJECT IS THE 2017 EDITION, NOT THE 2014 AS NOTED
 ON THE PLANS.WPB AMEND. TO FBC SEC. 101.4.
 4) THE PLANS SHOW A DENTAL OFFICE. DESCRIBE THE TYPE OF
 ACTIVITY THAT WILL TAKE PLACE IN THIS ROOM. WPB AMEND.
 TO FBC SEC. 107.2.1.
 5) SHT. P 1.0 - THE DRINKING FOUNTAIN IS NOT SHOWN ON
 THE SANITARY OR WATER RISER DIAGRAMS. WPB AMEND. TO FBC
 SEC. 107. 3.5.1.3.
 6) WHERE IS THE SERVICE SINK? A SERVICE SINK IS
 REQUIRED PER THE 2017 FBC-PLUMBING TABLE 403.1.
 7) THE "S-1" SINKS ARE INSTALLED ON A VERTICAL WET
 VENT. ONLY FIXTURES WITHIN A BATHROOM GROUP ARE
 PERMITTED TO BE INSTALLED ON A WET VENT PER 2017
 FBC-PLUMBING SEC.912.1.1. REFER TO THE DEFINITION OF
 ""BATHROOM GROUP" IN SECTION 202 OF THE PLUMBING CODE.
 8) PLEASE PROVIDE DIMENSIONS OF THE ROOMS INCLUDING THE
 TOILET ROOMS. FBC SEC. 107.2.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  