Plan Review Notes For Permit 18091065 |
Permit Number |
18091065 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-11-15 10:53:41 | 1) THE PLUMBING PLANS SHALL BEAR THE SEAL AND SIGNATURE | | OF THE DESIGN PROFESSIONAL OF RECORD PER FL. ADMIN. | | CODE RULE 61G15-23.001. | | 2) THE LEVEL OF ALTERATION SHALL BE LISTED ON THE PLANS | | PER THE 2017 FBC-EXISTING BUILDING CODE SEC.301.1. | | 3) SHT. LS 1.1 - THE EDITION OF CODES IN EFFECT FOR | | THIS PROJECT IS THE 2017 EDITION, NOT THE 2014 AS NOTED | | ON THE PLANS.WPB AMEND. TO FBC SEC. 101.4. | | 4) THE PLANS SHOW A DENTAL OFFICE. DESCRIBE THE TYPE OF | | ACTIVITY THAT WILL TAKE PLACE IN THIS ROOM. WPB AMEND. | | TO FBC SEC. 107.2.1. | | 5) SHT. P 1.0 - THE DRINKING FOUNTAIN IS NOT SHOWN ON | | THE SANITARY OR WATER RISER DIAGRAMS. WPB AMEND. TO FBC | | SEC. 107. 3.5.1.3. | | 6) WHERE IS THE SERVICE SINK? A SERVICE SINK IS | | REQUIRED PER THE 2017 FBC-PLUMBING TABLE 403.1. | | 7) THE "S-1" SINKS ARE INSTALLED ON A VERTICAL WET | | VENT. ONLY FIXTURES WITHIN A BATHROOM GROUP ARE | | PERMITTED TO BE INSTALLED ON A WET VENT PER 2017 | | FBC-PLUMBING SEC.912.1.1. REFER TO THE DEFINITION OF | | ""BATHROOM GROUP" IN SECTION 202 OF THE PLUMBING CODE. | | 8) PLEASE PROVIDE DIMENSIONS OF THE ROOMS INCLUDING THE | | TOILET ROOMS. FBC SEC. 107.2.1. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|