Plan Review Notes For Permit 18091065 |
Permit Number |
18091065 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-09-28 11:01:57 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) THERE ARE NO INDICATIONS OF EXISTING OR NEW EXIT | | SIGNAGE ALONG THE EGRESS TAVEL PATH. | | | | ENSURE PROPER PLACEMENT PER NFPA 101, CHAPTER 7, MEANS | | OF EGRESS. | | | | 7.10.2 DIRECTIONAL SIGNS. | | 7.10.2.1 A SIGN COMPLYING WITH 7.10.3, WITH A | | DIRECTIONAL | | INDICATOR SHOWING THE DIRECTION OF TRAVEL, SHALL BE | | PLACED IN EVERY | | LOCATION WHERE THE DIRECTION OF TRAVEL TO REACH THE | | NEAREST EXIT IS | | NOT APPARENT | | | | | | | | 2) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND | | SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY | | CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | 3) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | 4) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | 561-804-4709 | | [email protected] | | |
|