2018-10-05 14:39:26 | 1ST REVIEW FBC-2017 MECHANICAL |
| REVISION #18091057 |
| PERMIT #18030167 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET MEP-1: LABEL THE DIFFUSERS AND RETURNS USING |
| THE DEVICES SHOWN IN THE AIR DISTRIBUTION SCHEDULE, AND |
| PROVIDE THE SUPPLY AND RETURN CFMS AT EACH LOCATION- |
| SECTION 603.1 FBC M. |
| |
| 2) MEP-1: PROVIDE AN INSTALLATION DETAIL FOR THE NEW |
| FIRE DAMPER IN THE RETURN AND INDICATE HOW ACCESS WILL |
| BE PROVIDED- SECTIONS 607.4 & 607.5.2 FBC M. A) SUBMIT |
| SPECS FOR THE DAMPER- SECTION 607.2 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |