Plan Review Notes
Plan Review Notes For Permit 18091057
Permit Number 18091057
Review Stop M
Sequence Number 1
Notes
Date Text
2018-10-05 14:39:261ST REVIEW FBC-2017 MECHANICAL
 REVISION #18091057
 PERMIT #18030167
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MEP-1: LABEL THE DIFFUSERS AND RETURNS USING
 THE DEVICES SHOWN IN THE AIR DISTRIBUTION SCHEDULE, AND
 PROVIDE THE SUPPLY AND RETURN CFMS AT EACH LOCATION-
 SECTION 603.1 FBC M.
  
 2) MEP-1: PROVIDE AN INSTALLATION DETAIL FOR THE NEW
 FIRE DAMPER IN THE RETURN AND INDICATE HOW ACCESS WILL
 BE PROVIDED- SECTIONS 607.4 & 607.5.2 FBC M. A) SUBMIT
 SPECS FOR THE DAMPER- SECTION 607.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  