| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| APPROVED PROVISO: |
| |
| 1) THE DINING TENTS, SPECIFICALLY THE 40 X100 TENT |
| SHALL HAVE THE SEATING ARRANGED IN A MANNER THAT |
| COMPLIES WITH THE AISLE AND AISLEWAY REQUIREMENTS AS |
| LISTED UNDER NFPA 101: 12.2.5 (ARRANGEMENT OF MEANS OF |
| EGRESS). |
| |
| 2) THE OCCUPANT LOAD FOR THE 40 X 100 TENT SHALL COMPLY |
| WITH THE OCCUPANT LOAD FACTOR AS LISTED UNDER NFPA 101: |
| CHAPTER 7, TABLE 7.3.1.2. MORE SPECIFICALLY, ASSEMBLY |
| USE: LESS CONCENTRATED USE, WITHOUT FIXED SEATING - 15 |
| SQ FT/PERSON. |
| |
| 3) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE |
| OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. |
| |
| 4) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM |
| BUILDING STRUCTURES. |
| |
| 5) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, |
| OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS |
| ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. |
| |
| 6) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS |
| LOCATIONS. |
| |
| 7) GENERATORS AND OTHER INTERNAL COMBUSTION POWER |
| SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 |
| FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR |
| ENCLOSURE. |
| |
| 8) A FIRE INSPECTION CAN AND MAY BE CONDUCTED AFTER |
| SET-UP OF THE VENUE. |
| |
| |