Plan Review Notes For Permit 18090985 |
Permit Number |
18090985 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-09-26 08:31:50 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PANEL SHOWN IS ONLY 150 BUS RATED, OCP FOR PV ARRAY IS | | 50A? | | | | 50 X 125% + 125 = 187A 150 X 120% = 180A | | | | 705.12(D)(3)(2)(B) | | (B) WHERE TWO SOURCES, ONE A UTILITY AND THE OTHER AN | | INVERTER, ARE LOCATED AT OPPOSITE ENDS OF A BUSBAR THAT | | CONTAINS | | LOADS, THE SUM OF 125 PERCENT OF THE INVERTER(S) OUTPUT | | CIRCUIT | | CURRENT AND THE RATING OF THE OVERCURRENT DEVICE | | PROTECTING THE | | BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF | | THE | | BUSBAR. THE BUSBAR SHALL BE SIZED FOR THE LOADS | | CONNECTED IN | | ACCORDANCE WITH ARTICLE 220. A PERMANENT WARNING LABEL | | SHALL | | BE APPLIED TO THE DISTRIBUTION EQUIPMENT ADJACENT TO | | THE BACKFED | | BREAKER FROM THE INVERTER THAT DISPLAYS THE FOLLOWING | | OR | | EQUIVALENT WORDING: |
|